Power factor is the cosine of the angle by which phase current leads or lags phase voltage in an AC circuit. It equals 1.0 when power flows into a purely resistive load. It can also be written as active power divided by apparent power, that is kW over kVA. Meters and protective relays report power factor for each phase and for all three phases together, with a flag showing whether it is leading or lagging. Inverter datasheets such as the Fronius Symo list an adjustable power factor range from 0 to 1, inductive or capacitive. Changing an inverter's power factor setpoint changes its reactive power output. Running PV at an absorbing power factor helps hold down the voltage rise that comes with more real power export. Other control options are power factor scheduling and the PF(P) curve mode, where the power factor changes as the active power changes. If the operating range is limited to 0.85 inductive through 0.85 capacitive, the inverter's MVA rating has to be based on the plant's maximum MW output at 0.85 power factor.

<!-- review notes

Claims

related_to

c1 drafted · lead Apparent power

Power factor is the ratio of active power to apparent power (kW / kVA).

c2 drafted · lead Active power

Active power is the numerator of the power factor ratio.

c3 drafted · lead Reactive power

Changing the power factor setpoint changes the inverter's reactive power output.

c4 verified · fact Constant power factor mode

verified by: review-workflowverified on: 2026-10-24

c5 drafted · lead Watt-power factor

In PF(P) curve mode the power factor follows the active power output.

c6 verified · fact Voltage rise

Running PV at an absorbing power factor helps offset the voltage rise caused by real power injection.

verified by: review-workflowverified on: 2026-10-24