A power factor penalty is an extra charge some utilities add to a customer's bill when the site has a low power factor or draws a lot of reactive power. Utilities have to supply both real and reactive power but bill customers only for real power, so penalties recover the cost of the reactive power. The penalty grows with the amount of reactive power supplied. Inductive loads such as motors, transformers, pumps and air conditioners need reactive power, and that pulls the power factor down. Adding PV can make the problem worse. An inverter running at unity power factor reduces the active power taken from the grid, but the reactive power drawn stays the same, so the meter at the grid connection point reads a lower power factor. The penalty can also come from PV output that bypasses the feedback of an automatic power factor correction panel, or from harmonic distortion caused by non-linear loads. Fixes include capacitors installed on the customer side of the meter, sending PV output through the correction feedback, and setting a power factor on the inverters. An external controller can also adjust inverter PF and reactive power over Modbus. Not every utility charges for low power factor. Where the utility installs the capacitors itself, the customer still pays a reactive energy fee.

Claims

related_to

c1 drafted · lead Power factor

The penalty is charged when the customer's power factor is low.

c2 drafted · lead Reactive power

Utilities bill only real power, so penalties cover the reactive power they supply; penalties scale with that reactive power.

c3 drafted · lead Low meter power factor

With PV feeding at unity power factor, grid active power falls while reactive draw stays the same, so the grid-point meter records a lower power factor and the customer can be penalized.

c4 drafted · lead Constant power factor mode

One fix: set the inverter power factor to the plant's no-solar value, with the direction opposite to the plant power factor.

review note: support check: partial - u16 says set inverter PF equal to the no-solar value with opposite direction, but doesn't name constant power factor mode explicitly; core is stated.

c5 drafted · lead Harmonic distortion

Harmonics from non-linear loads lower the true power factor even more.

c6 drafted · lead Modbus

An external controller can adjust inverter PF and Q setpoints over Modbus as conditions change.

c7 drafted · lead Energy meter

The meter at the grid connection point measures power factor; a billing meter can compute an average power factor over the billing period.

review note: support check: partial - Grid-connection-point meter PF is supported (u16) and billing-period average PF by KV2C (u28), but u28 doesn't link to penalties and 'billing meter' framing is loose.