Solar Lattice

Component

Grid tie relay

ID
comp:grid-relay
IRI
https://solarlattice.org/kb/comp/grid-relay
Status
active
Also known as
Grid relay, Line tie relay, Inverter relay, Inv Relay

The grid tie relay is the switch inside the inverter that connects its output to the utility grid and disconnects it again. Some grid operators require a signal as soon as the inverter connects to the grid. On SMA inverters the multifunction relay can be set to report the grid relay's switching status for this purpose. The main failure mode is relay failure: the relay contacts weld shut or stay open. CPS inverters report grid relay problems as Fault0100 (grid relay fault) or Protect0020 (grid relay error). Some models also use Protect0120, Protect0130 or PFault0030 for grid or inverter relay faults. The recommended first step is to switch both the AC and DC switches off, wait for stored energy to discharge, and then switch both back on. The manuals give a wait of 1 minute or 5 minutes depending on the model. If the fault does not clear after the restart, CPS manuals say to replace the inverter or, on some models, to contact after-sales service.