Solar Lattice

Symptom

Hotspot in IR image

ID
symptom:hotspot-ir-image
IRI
https://solarlattice.org/kb/symptom/hotspot-ir-image
Status
active
Also known as
hot spots, thermal abnormalities, thermal anomaly

A hotspot is a part of a module, connection or other component that shows up hotter than its surroundings in an infrared image taken while the system is under load. Scan in clear, stable weather with high irradiance and the inverter running. Avoid reflections from clouds and nearby objects, then compare the module with its neighbours in the same string. A hot cell or a hot localized area points to cracked cells, broken front glass, solder bond or cell interconnection faults, or mismatch that forces cells into reverse bias. Hot junction box terminals, connectors, cables or fuse clamps usually mean a loose or poor electrical connection, not a fault in the cells. A warm substring or a heated bypass diode suggests the diode is conducting. Check first for shading or debris on that module, and suspect a bad module or a shorted diode if none is found. Treat one thermal image as a screening result only. Confirm it with string current, the IV curve shape and visual inspection, and add EL imaging where cell damage is suspected. Raise the priority when the hotspot appears again on later inspections, when several modules in one string show it, or when there is a safety risk, because strong hotspots can lead to smouldering fires.

<!-- review notes

Claims

observed_as

c1 drafted · lead Localized IR hotspot

Localized heating during loaded operation; linked to poor solder joints, cracked cells, poor connections or severe mismatch inside a module.

c2 drafted · lead Hot cell in IR image

Broken front glass often leaves broken hot cells in the damaged module; cracked cells also show as hot cells.

c3 verified · fact Warm substring in IR image

Inactive substrings or modules look warmer than active parts, but the difference is small and grows with irradiance, so low-irradiance scans can miss it.

verified by: joshuahamsaverified on: 2026-10-20

c4 verified · fact Hot electrical connection

Covers junction box terminals with loose internal connections, overheated DC connectors, cables and fuse clamps.

verified by: joshuahamsaverified on: 2026-10-20