A gradual performance decline is a slow fall in irradiance-normalized production while the plant stays online. Track performance ratio trends and normalized output against rain and cleaning records, soiling station data and model residuals. If the decline builds up during dry periods and recovers partly or fully after real rain or washing, dust soiling is the likely cause. Do not judge soiling from one dirty irradiance sensor, because sensor drift or local obstruction can look like soiling. A decline that lasts for years and runs faster than the module warranty rate can point to system-level degradation: modules age at different rates, and the weaker ones limit the current of their strings. To separate this from average module ageing, compare string or inverter trends, IV curve data and module test results. Broken glass may not cut power at first, but moisture getting in later speeds up corrosion and degradation, so check the rear glass visually and watch for insulation faults. Potential induced degradation usually shows up after commissioning and can strongly reduce string performance.

<!-- review notes

Claims

observed_as

c1 verified · fact Declining performance ratio

For dust soiling, irradiance-normalized production falls slowly through dry periods; compare performance ratio trends and model residuals for dry accumulation periods.

verified by: joshuahamsaverified on: 2026-10-20

c2 verified · fact Production recovery after rain

Soiling-driven decline is often partly or fully recovered after meaningful rain or washing.

verified by: joshuahamsaverified on: 2026-10-20

c3 drafted · lead Long-term normalized output decline

For system vs module degradation, long-term normalized plant output and string or inverter trends decline faster than the module nameplate degradation rate.

review note: support check: partial - Passages support comparing long-term normalized output and string/inverter trends and system degradation exceeding nameplate, but not the specific yearly energy or string current spread signals.

degradation_rate

c4 verified · fact nominal 0.1 PERCENT-PER-YR

Conditions: Allowance some independent engineers add to the module degradation rate to cover mismatch from modules degrading at different rates; a modeling allowance, not a universal rule.

verified by: joshuahamsaverified on: 2026-10-20

typical_power_loss

c5 verified · fact 1–2 PERCENT

Conditions: Loss from glass breakage events in temperate climates, per the Herz et al. study.

verified by: joshuahamsaverified on: 2026-10-20review note: reviewer: the compiler-flagged conflict is a different scenario or technology, not disagreement

c6 verified · fact 20–80 PERCENT

Conditions: Reduction of PV string performance from potential induced degradation after commissioning, per Libby et al.; source states it as up to 20-80%.

verified by: joshuahamsaverified on: 2026-10-20review note: reviewer: the compiler-flagged conflict is a different scenario or technology, not disagreement