FailureMode
Temperature sensor fault
- ID
fm:temperature-sensor-fault
- IRI
https://solarlattice.org/kb/fm/temperature-sensor-fault
- Status
- active
- Also known as
- TempSensorErr, Warn0050
The inverter raises a TempSensorErr alarm, also listed as Warn0050, when it detects an abnormal temperature reading. The usual causes are poor contact at the temperature sensor's socket connector or a damaged sensor. One manual also lists a sensor reading of -25C as a possible cause. To confirm it, look at the temperature value on the inverter display and check whether it makes sense. Turn the external AC disconnect off and back on to reboot the inverter, and see whether the alarm clears. If the alarm stays after the reboot, contact the manufacturer's service team.
<!-- review notes
- sentence 4: support check: partial - Passages say observe/verify the temperature display, but not explicitly to check whether it makes sense.
- sentence 5: support check: partial - Reboot via external AC disconnect is stated, but 'see whether the alarm clears' is only implied by the later contact-if-not-corrected step.
-->
Claims
affects
c1 verified · fact
Temperature sensor
verified by: review-workflowverified on: 2026-10-20
c2 verified · fact
Inverter
The sensor involved is the inverter's internal temperature sensor.
verified by: review-workflowverified on: 2026-10-20review note: support check: partial - u16 mentions an internal temperature sensor with poor contact, but the passage doesn't state the fault affects the inverter beyond raising an alarm.
caused_by
c3 verified · fact
Poor connector contact
Poor contact at the temperature sensor's socket connector.
verified by: review-workflowverified on: 2026-10-20
presents_as
c4 drafted · lead
Abnormal temperature reading
Flagged as the TempSensorErr alarm. One manual lists a sensor reading of -25C as a possible cause.
detected_by
c5 verified · fact
Inverter display check
Check the temperature value shown on the inverter display.
verified by: review-workflowverified on: 2026-10-20
mitigated_by
c6 verified · fact
Inverter restart
Turn the external AC disconnect (or the working power supply) off and back on to reboot the system.
verified by: review-workflowverified on: 2026-10-20
c7 verified · fact
Contact manufacturer service
Use this step if a reboot does not clear the alarm.
verified by: review-workflowverified on: 2026-10-20