Meter CT ratio misconfiguration

ID
fm:meter-ct-ratio-misconfiguration
IRI
https://solarlattice.org/kb/fm/meter-ct-ratio-misconfiguration
Status
active
Also known as
incorrect CT ratio, meter ratio issue, Set Meter CT, wrong CT primary setting, Wrong Rating

This fault means the current transformer ratio stored in the energy meter does not match the CTs actually installed. It often happens when the installer fits their own CTs but leaves the meter's default ratio in place. The usual sign is meter or grid-connection readings that are much too low or too high for the real loads. To confirm it, read the CT and VT ratio set in the meter. Check that any monitoring platform uses the same ratio as the meter. The correct ratio is the CT primary current divided by its secondary current. For example, 150A:5A CTs need a ratio of 30. Enter the correct ratio through the meter's setup menu and save it. On systems with a meter, set the ratio on the meter itself, not on the inverter. If the current still reads only a small fraction of what you expect, check whether the CT shorting tabs are still engaged.

<!-- review notes

Claims

affects

c1 drafted · lead Energy meter

c2 drafted · lead Current sensor

The ratio entered must match the installed current transformer rating, e.g. 150A:5A or 300/5A.

review note: support check: partial - Passages say the ratio must match the installed CT (e.g. 300/5A, 150A:5A), but do not say misconfiguration affects the current sensor component itself.; review: partial - The note (the ratio must match the installed CT, e.g. 150A:5A or 300/5A) is supported, but the passages say only that wrong readings show on the meter, not that the misconfiguration affects the current sensor itself.

presents_as

c3 drafted · lead Unrealistic meter values proposed

Meter or point-of-connection readings look very low or very high compared with the real loads.

caused_by

c4 drafted · lead Meter configuration error proposed

review note: support check: partial - Passages list wrong meter configuration info and wrong CT rating as common problems, but don't explicitly state CT ratio misconfiguration is caused by it.

c5 verified · fact Installation error

Fitting CTs other than the supplied ones without changing the default ratio on the meter.

verified by: review-workflowverified on: 2026-10-24

detected_by

c6 drafted · lead Meter configuration check proposed

Check the CT and VT ratio on the meter, and make sure the monitoring platform uses the same ratio as the meter.

mitigated_by

c7 drafted · lead Meter configuration correction proposed

Set the ratio to primary current divided by secondary current, for example 30 for 150A:5A CTs, then save it.