Symptom
Fallback operation after loss of control or meter signal
- ID
symptom:control-fallback-operation
- IRI
https://solarlattice.org/kb/symptom/control-fallback-operation
- Status
- active
- Also known as
- Communication with the System Manager failed, timeout in communication for active power limitation, fallback mode, LimByEPM, fallback level, reactive power setpoint timeout, failsafe, restricted function, Loss of Meter Communication, Fallback activated
Fallback operation happens when an inverter or plant controller loses its energy meter, its system manager or its external setpoint. Instead of following live control, it switches to a predefined behaviour. In monitoring data, output either holds flat at a set fallback power or at the last received values, or drops to zero when a failsafe shutdown is configured. Look for SMA event 8708 or a fallback activated status, a flashing red LED warning, or a Failsafe or LimByEPM message on Solis displays. Likely causes are a meter that has failed or lost power, a damaged or unplugged communication cable between the inverter and the system manager, or an external setpoint that is missing or invalid. If output stays limited while the meter communicates normally, check the failsafe and EPM settings. Solis advises turning both the external and internal EPM fail safe options off when they are not needed. Start by checking that the meter is powered, then inspect the network connection and cables to the controller, and confirm the meter settings. Normal operation resumes once communication has been back for the configured re-entry time.
<!-- review notes
- sentence 3: support check: partial - Event 8708, the fallback activated status, the red flashing LED and the Failsafe alarm are in the passages, and LimByEPM is mentioned; but the passages never say 'Solis displays' show these, and 8708 isn't tied to a fallback-activated status.
- sentence 4: support check: partial - Passages support a damaged or unplugged communication cable to the system manager and a missing or invalid setpoint, but a meter that has failed or lost power is only implied by the 'verify meter is powered on' step, not stated as a cause.
- sentence 5: support check: partial - Solis advice to turn the external and internal EPM fail safe settings off is stated, but 'when not needed' and the 'meter communicates normally' condition are not in the passages.
- sentence 4: review: partial - The damaged or unplugged cable to the system manager and the missing or invalid setpoint are stated, but a failed or unpowered meter is only implied by Tesla's loss-of-meter-communication alert and its 'verify meter is powered on' step, not stated…
-->
Claims
observed_as
c1 verified · fact
Flat output below available power
In fallback the inverter holds AC output at a configured fallback setpoint, or at the last received values, until the trigger has stayed clear for the re-entry time.
verified by: review-workflowverified on: 2026-10-24review note: support check: partial - Fallback setpoint hold and re-entry time are stated, but the passages say nothing about irradiance staying normal/rising or power staying flat regardless of irradiance; the 'last received values' option is also covered.
c2 verified · fact
Zero inverter AC output
With failsafe ON, losing the meter or CT shuts generation down. Tesla systems curtail output to zero when the lost meter is needed by the active control function.
verified by: review-workflowverified on: 2026-10-24
c3 verified · fact
Fallback event message proposed
Examples are SMA event 8708 (timeout in communication for active power limitation) and Inverter Manager status IDs 2055/2056 (fallback activated/completed).
verified by: review-workflowverified on: 2026-10-24
c4 drafted · lead
Inverter fault code display
Solis displays show a Failsafe alarm when the CT or meter disconnects with failsafe ON, or a LimByEPM message when external power meter limiting is active.
review note: support check: partial - The Failsafe alarm on the LCD is stated and a LimByEPM message is mentioned, but the passages do not say it appears when external power meter limiting is active (only that it can occur when the setting is on).; review: partial - The Failsafe LCD alarm on CT/meter disconnect with failsafe ON is stated, but the passages only say LimByEPM can occur when the external power meter setting is on, not that it shows when meter limiting is active or that it…
c5 verified · fact
Inverter fault indicator light
A flashing red LED pattern warns that communication with the System Manager failed and that the inverter is running with restricted function.
verified by: review-workflowverified on: 2026-10-24
c6 verified · fact
Frozen meter readings proposed
After loss of meter communication, the reported meter values stay frozen at their last value.
verified by: review-workflowverified on: 2026-10-24
c7 drafted · lead
Meter invalid alert proposed
A Meter Invalid alert is raised on loss of meter communication, out-of-bounds or unreasonable readings, or a PT/CT failure, and control elements are then disabled.