Emergency stop circuit defect

ID
fm:emergency-stop-defect
IRI
https://solarlattice.org/kb/fm/emergency-stop-defect
Status
active
Also known as
Defective fast stop

This failure is a defect in the emergency stop circuit, also called the fast stop. On SMA Sunny Central CP-XT inverters it is reported as error 9019. The inverter can show an emergency stop status even when no one has pressed the button, and an internal inverter fault is one listed cause. Before going further, check that the emergency stop button really is released. For error 9019, the manual says to check the fast stop cabling. Test each emergency switch, on the cabinet and outside it. With the circuit healthy, both signal lights on the emergency stop relay should be lit, and they should go off when a switch is operated. In plants where several inverters run in a Team configuration, the emergency stop relay must switch in every cabinet. If the stop status is still there after the button is reset, contact the manufacturer's service center.

<!-- review notes

Claims

affects

c1 verified · fact Emergency stop circuit

SMA Sunny Central CP-XT error 9019 reports a defective fast stop.

verified by: review-workflowverified on: 2026-10-23

presents_as

c2 drafted · lead Emergency stop triggered

The inverter can show an emergency stop status when the button was not pressed. The manual lists an internal inverter fault as the other possible cause.

detected_by

c3 verified · fact Emergency stop functional test

Operate each emergency switch, both on the cabinet and external ones. In normal operation both signal lights on the emergency stop relay should be lit, and they should go off when a switch or door contact is opened. In Team configurations the relay must switch in every cabinet.

verified by: review-workflowverified on: 2026-10-23

c4 drafted · lead Visual inspection

When output is abnormal, check what state the emergency stop button is in.

review note: review: partial - The Sungrow passage says to check the state of the emergency stop button when power output is abnormal, but that is a check on whether the button is engaged, not a stated way to detect a defect in the circuit.

mitigated_by

c5 verified · fact Wiring and terminal check

For error 9019, the corrective measure is to check the fast stop cabling.

Check the fast stop cabling.

verified by: review-workflowverified on: 2026-10-23

c6 verified · fact Contact manufacturer service

Contact after-sales service if the emergency stop status remains after the button has been reset.

verified by: review-workflowverified on: 2026-10-23