The emergency stop functional test checks each emergency switch in turn: the ones on the cabinet, the ones in the stations and any external emergency stop switches. Before testing, set the inverter to Stop, open the doors, and make sure control voltage is present. Also check that the external emergency stop is not activated, and tape the door contact switches in the On position. In normal operation both relay signal lights are on. When a switch is pressed, the relay lights should change to OFF and the controller should show error 206, which needs manual acknowledgement. Where several inverters work in a Team configuration, the emergency stop relay must switch in every cabinet. On some inverters, pressing the emergency stop opens the DC load switches and AC circuit breakers. The button stays locked until it is released with a key. Afterwards, unlock the switch, acknowledge the error, remove the tape from the door contacts and close the cabinet doors. The cabinet is live during the test and there is a risk of fatal electric shock or burns, so touch only the parts named in the instructions.

<!-- review notes

Claims

produces

c1 verified · fact Emergency stop relay lights off

In normal operation both signal lights of the emergency switch relay are lit. When a switch is pressed during the test, the relay indicator lights should change to OFF.

verified by: review-workflowverified on: 2026-10-23

c2 verified · fact Inverter fault code display

On the Sunny Central, activating the emergency switch should bring up error 206 on the controller. The error must be acknowledged manually.

verified by: review-workflowverified on: 2026-10-23

Referenced by

Data