The Enphase IQ System Controller, previously called Enpower, is a smart switch that ties the home to grid power, IQ Battery storage and solar PV. It works as a microgrid interconnect device: when the grid fails it detects the outage and moves the home to backup power automatically. The family includes the original unit, IQ System Controller 2, 3, 3G and 3M, and each version has its own SKU. On the IQ System Controller 3 the third DER port takes extra PV and IQ Battery 5P. On the 3G that port takes a generator instead. IQ System Controller 2 has PV, storage and generator input circuits, plus a neutral-forming transformer for 120/240 V operation in backup. You can install several controllers on one site, but only in parallel, never in series, and each one needs its own Enlighten site ID. Known troubleshooting topics include the controller not reporting, rapid shutdown issues and power cycling.

Claims

instance_of

c1 drafted · lead Transfer switch controller

Provides microgrid interconnect device (MID) functionality.

implements

c2 drafted · lead Automatic backup transfer

Detects grid failure and moves the home from grid power to backup power automatically.

c3 drafted · lead Generator support

Generator input circuit on IQ System Controller 2; on the 3G the third DER port supports generator integration.

compatible_with

c4 drafted · lead Enphase IQ8 Series Microinverters proposed

c5 drafted · lead Enphase IQ Gateway

Gateway communicates with the controller; a wireless communications kit at 2.4 GHz enables direct communication.

c6 drafted · lead 120/240 V split-phase service

Scope: applications backup

A neutral-forming transformer enables 120/240 V operation in backup mode.

requires

c7 drafted · lead PV rapid shutdown

Scope: products Enphase IQ8 Series Microinverters proposed

Conditions: Systems with IQ8 Microinverters and an IQ System Controller 2 must use a Rapid Shutdown switch.