Zero-sequence imbalance
Zero-sequence imbalance is a revenue meter quantity, given in percent, that compares the zero-sequence component of the three phase voltages or currents with their positive-sequence component. The meter reports it separately for voltage and for current, and it updates both values every 10/12 cycles. Aggregated versions of both values are also available, and they update at a rate set by the chosen aggregation period. The meter also calculates negative-sequence imbalance, so read the two signatures side by side when checking a phase imbalance. On delta-connected voltage inputs, the zero-sequence voltage cannot be calculated, so a zero reading there does not mean the phases are balanced. Form 5 meters always report zero for the zero-sequence voltage imbalance because the quantity is undefined for delta connections.