Hazard
Energized PV array in daylight
- ID
hazard:energized-pv-array
- IRI
https://solarlattice.org/kb/hazard/energized-pv-array
- Status
- active
- Also known as
- PV modules energized when illuminated, live DC conductors, up to 90 V DC on module leads
- Category
- Electrical
Whenever light falls on PV modules, the array produces a dangerous DC voltage that can kill. That voltage is on the DC conductors and on live parts inside the inverter. Unlike an AC circuit, the array's DC circuits are live all through daylight and cannot be isolated at the source. Some tasks, such as insulation tests and I-V measurements, therefore have to be done on energized circuits. Microinverter systems carry the same warning: the DC conductors are ungrounded and may be energized when module leads are connected. Do not touch DC conductors, bare cable ends or live inverter parts. Disconnect the inverter from all voltage sources before working on it, and leave installation and fault repair to qualified persons. Work de-energized under lockout/tagout where you can. When you must work live, wear rubber insulating gloves, a Class E hardhat, EH-rated footwear and safety glasses, and use insulated tools. During live testing, keep other people out of the work area, and do not touch module frames, backsheets or terminals while the test is running. Rapid shutdown lowers the shock risk from conductors outside the array. Labels warn, however, that conductors inside the array stay energized in sunlight.
<!-- review notes
- sentence 2: support check: partial - u2 and u13 support live DC circuits that cannot be isolated and unavoidable energized measurements, but I-V measurements are not named explicitly as a live task (u25 only mentions the lethal shock hazard); "at the source" is also a slight paraphrase.
- sentence 3: support check: partial - The DANGER text about ungrounded, possibly energized DC conductors appears in the Enphase microinverter instructions, but the passages do not say it is the "same warning" as for other systems, and "when module leads are connected" is only loosely implied.
- sentence 5: support check: partial - LOTO, gloves, Class E hardhat, EH footwear, safety glasses and insulated tools are all in u13, but "rubber" gloves is not stated, and the passages do not give the live-work PPE set as one directive.
-->
Claims
subclass_of
c1 drafted · lead
Electric shock
Sunlight on the PV modules produces a DC voltage high enough to kill, so touching DC conductors or live inverter parts can cause a fatal shock.
controlled_by
c2 drafted · lead
Rubber insulating gloves
Wear these when working on or testing energized PV circuits. The PPE level needed depends on the circuit voltage and fault current.
c3 drafted · lead
Insulated hand tools
c4 verified · fact
Lockout/tagout devices
Work de-energized under documented lockout/tagout wherever that is possible.
verified by: review-workflowverified on: 2026-10-24
c5 verified · fact
Hard hat
The guide calls for a nonconductive Class E hardhat.
verified by: review-workflowverified on: 2026-10-24
c6 verified · fact
Safety glasses
verified by: review-workflowverified on: 2026-10-24
c7 verified · fact
PV rapid shutdown proposed
Rapid shutdown de-energizes controlled conductors outside the array boundary. On systems that shut down only the conductors leaving the array, the conductors inside the array stay energized in sunlight.
verified by: review-workflowverified on: 2026-10-24