Solar Lattice

Hazard

Energized PV array in daylight

ID
hazard:energized-pv-array
IRI
https://solarlattice.org/kb/hazard/energized-pv-array
Status
active
Also known as
PV modules energized when illuminated, live DC conductors, up to 90 V DC on module leads
Category
Electrical

Whenever light falls on PV modules, the array produces a dangerous DC voltage that can kill. That voltage is on the DC conductors and on live parts inside the inverter. Unlike an AC circuit, the array's DC circuits are live all through daylight and cannot be isolated at the source. Some tasks, such as insulation tests and I-V measurements, therefore have to be done on energized circuits. Microinverter systems carry the same warning: the DC conductors are ungrounded and may be energized when module leads are connected. Do not touch DC conductors, bare cable ends or live inverter parts. Disconnect the inverter from all voltage sources before working on it, and leave installation and fault repair to qualified persons. Work de-energized under lockout/tagout where you can. When you must work live, wear rubber insulating gloves, a Class E hardhat, EH-rated footwear and safety glasses, and use insulated tools. During live testing, keep other people out of the work area, and do not touch module frames, backsheets or terminals while the test is running. Rapid shutdown lowers the shock risk from conductors outside the array. Labels warn, however, that conductors inside the array stay energized in sunlight.

<!-- review notes

Claims

subclass_of

c1 drafted · lead Electric shock

Sunlight on the PV modules produces a DC voltage high enough to kill, so touching DC conductors or live inverter parts can cause a fatal shock.

controlled_by

c2 drafted · lead Rubber insulating gloves

Wear these when working on or testing energized PV circuits. The PPE level needed depends on the circuit voltage and fault current.

c3 drafted · lead Insulated hand tools

c4 verified · fact Lockout/tagout devices

Work de-energized under documented lockout/tagout wherever that is possible.

verified by: review-workflowverified on: 2026-10-24

c5 verified · fact Hard hat

The guide calls for a nonconductive Class E hardhat.

verified by: review-workflowverified on: 2026-10-24

c6 verified · fact Safety glasses

verified by: review-workflowverified on: 2026-10-24

c7 verified · fact PV rapid shutdown proposed

Rapid shutdown de-energizes controlled conductors outside the array boundary. On systems that shut down only the conductors leaving the array, the conductors inside the array stay energized in sunlight.

verified by: review-workflowverified on: 2026-10-24

Data