Voltage trip disconnects the inverter from the grid when the voltage stays outside set overvoltage or undervoltage limits for longer than the set clearing time. Utilities can require their own settings. For example, PPL EU sets OV1 at 1.1 p.u. with a 2.1 s trip time and UV2 at 0.5 p.u. with a 0.6 s trip time.

<!-- review notes

Claims

trip_threshold

c1 verified · fact nominal 1.2 UNITLESS

Scope: standard IEEE 1547-2018 proposed

Conditions: OV2 shall-trip function, Category I and Category II; per-unit of nominal voltage; the setting is fixed at this value

verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c3 (same source; check the conditions); possible conflict with c7 (same source; check the conditions); possible conflict with c11 (same source; check the conditions); possible conflict with c15 (same source; check the conditions)

c3 drafted · lead nominal 1.1 UNITLESS

Scope: standard IEEE 1547-2018 proposed

Conditions: OV1 default setting, Category I and Category II; per-unit of nominal voltage

review note: possible conflict with c1 (same source; check the conditions); possible conflict with c7 (same source; check the conditions); possible conflict with c11 (same source; check the conditions); possible conflict with c15 (same source; check the conditions)

c7 drafted · lead nominal 0.45 UNITLESS

Scope: standard IEEE 1547-2018 proposed

Conditions: UV2 default setting, Category I and Category II; per-unit of nominal voltage

review note: possible conflict with c1 (same source; check the conditions); possible conflict with c3 (same source; check the conditions); possible conflict with c11 (same source; check the conditions); possible conflict with c15 (same source; check the conditions)

c11 drafted · lead nominal 0.7 UNITLESS

Scope: standard IEEE 1547-2018 proposed

Conditions: UV1 default setting, Category II; per-unit of nominal voltage

review note: possible conflict with c1 (same source; check the conditions); possible conflict with c3 (same source; check the conditions); possible conflict with c7 (same source; check the conditions); possible conflict with c15 (same source; check the conditions)

c15 drafted · lead nominal 0.5 UNITLESS

Scope: standard IEEE 1547-2018 proposed

Conditions: UV2 default setting, Category III; per-unit of nominal voltage

review note: possible conflict with c1 (same source; check the conditions); possible conflict with c3 (same source; check the conditions); possible conflict with c7 (same source; check the conditions); possible conflict with c11 (same source; check the conditions)

c17 drafted · lead nominal 1.1 UNITLESS

Conditions: PPL EU required OV1 shall-trip setting; per-unit of nominal voltage

review note: possible conflict with c19 (same source; check the conditions); possible conflict with c21 (same source; check the conditions); possible conflict with c23 (same source; check the conditions)

c19 verified · fact nominal 1.2 UNITLESS

Conditions: PPL EU required OV2 shall-trip setting; per-unit of nominal voltage

verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c17 (same source; check the conditions); possible conflict with c21 (same source; check the conditions); possible conflict with c23 (same source; check the conditions)

c21 verified · fact nominal 0.88 UNITLESS

Conditions: PPL EU required UV1 shall-trip setting; per-unit of nominal voltage

verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c17 (same source; check the conditions); possible conflict with c19 (same source; check the conditions); possible conflict with c23 (same source; check the conditions)

c23 drafted · lead nominal 0.5 UNITLESS

Conditions: PPL EU required UV2 shall-trip setting; per-unit of nominal voltage

review note: possible conflict with c17 (same source; check the conditions); possible conflict with c19 (same source; check the conditions); possible conflict with c21 (same source; check the conditions)

c34 drafted · lead nominal 110 PERCENT

Scope: products Generac pwrmicro proposed

Conditions: OV1 voltage trip, percent of nominal, Generac PWRmicro

trip_time

c2 drafted · lead nominal 0.16 SEC

Scope: standard IEEE 1547-2018 proposed

Conditions: OV2 clearing time, Category I and Category II; the setting is fixed at this value

review note: possible conflict with c5 (same source; check the conditions); possible conflict with c13 (same source; check the conditions); possible conflict with c16 (same source; check the conditions)

c5 verified · fact nominal 2 SEC

Scope: standard IEEE 1547-2018 proposed

Conditions: OV1 default clearing time, Category I and Category II

verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c2 (same source; check the conditions); possible conflict with c9 (same source; check the conditions); possible conflict with c13 (same source; check the conditions)

c9 verified · fact nominal 0.16 SEC

Scope: standard IEEE 1547-2018 proposed

Conditions: UV2 default clearing time, Category I and Category II

verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c5 (same source; check the conditions); possible conflict with c13 (same source; check the conditions); possible conflict with c16 (same source; check the conditions)

c13 verified · fact nominal 10 SEC

Scope: standard IEEE 1547-2018 proposed

Conditions: UV1 default clearing time, Category II

verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c2 (same source; check the conditions); possible conflict with c5 (same source; check the conditions); possible conflict with c9 (same source; check the conditions); possible conflict with c16 (same source; check the conditions)

c16 drafted · lead nominal 2 SEC

Scope: standard IEEE 1547-2018 proposed

Conditions: UV2 default clearing time, Category III

review note: possible conflict with c2 (same source; check the conditions); possible conflict with c9 (same source; check the conditions); possible conflict with c13 (same source; check the conditions)

c18 verified · fact nominal 2.1 SEC

Conditions: PPL EU required OV1 shall-trip time

verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c20 (same source; check the conditions); possible conflict with c24 (same source; check the conditions)

c20 drafted · lead nominal 0.16 SEC

Conditions: PPL EU required OV2 shall-trip time

review note: possible conflict with c18 (same source; check the conditions); possible conflict with c22 (same source; check the conditions); possible conflict with c24 (same source; check the conditions)

c22 drafted · lead nominal 2.1 SEC

Conditions: PPL EU required UV1 shall-trip time

review note: possible conflict with c20 (same source; check the conditions); possible conflict with c24 (same source; check the conditions)

c24 drafted · lead nominal 0.6 SEC

Conditions: PPL EU required UV2 shall-trip time

review note: possible conflict with c18 (same source; check the conditions); possible conflict with c20 (same source; check the conditions); possible conflict with c22 (same source; check the conditions)

c27 verified · fact nominal 13 SEC

Scope: products CPS SCA100K-T-US-480 / SCA50K-T-US-208; standard IEEE 1547 proposed

Conditions: VoltMaxTripT1, IEEE 1547 profile

verified by: review-workflowverified on: 2026-10-24

c28 drafted · lead nominal 12.5 SEC

Scope: products CPS SCA100K-T-US-480 / SCA50K-T-US-208; standard CA Rule 21 proposed

Conditions: VoltMaxTripT1, Rule 21 profile

c29 drafted · lead nominal 2 SEC

Scope: products CPS SCA100K-T-US-480 / SCA50K-T-US-208

Conditions: VoltMaxTripT1, ISO-NE profile

review note: possible conflict with c31 (same source; check the conditions)

c31 drafted · lead nominal 0.16 SEC

Scope: products CPS SCA100K-T-US-480 / SCA50K-T-US-208

Conditions: VoltMaxTripT2 and VoltMaxTripT3 in IEEE 1547, Rule 21 and ISO-NE profiles

review note: possible conflict with c29 (same source; check the conditions)

c35 drafted · lead nominal 13 SEC

Scope: products Generac pwrmicro proposed

Conditions: OV1 clearing time, Generac PWRmicro

setting_range

c4 verified · fact 1.1–1.2 UNITLESS

Scope: standard IEEE 1547-2018 proposed

Conditions: OV1 allowable voltage settings, Category I and Category II; per-unit of nominal voltage

verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c8 (same source; check the conditions); possible conflict with c12 (same source; check the conditions)

c6 drafted · lead 1–13 SEC

Scope: standard IEEE 1547-2018 proposed

Conditions: OV1 allowable clearing time settings, Category I and Category II

c8 drafted · lead 0–0.5 UNITLESS

Scope: standard IEEE 1547-2018 proposed

Conditions: UV2 allowable voltage settings, Category I, II and III; per-unit of nominal voltage

review note: possible conflict with c4 (same source; check the conditions)

c10 drafted · lead 0.16–2 SEC

Scope: standard IEEE 1547-2018 proposed

Conditions: UV2 allowable clearing time settings, Category I and Category II

c12 drafted · lead 0–0.88 UNITLESS

Scope: standard IEEE 1547-2018 proposed

Conditions: UV1 allowable voltage settings, Category II; per-unit of nominal voltage

review note: possible conflict with c4 (same source; check the conditions)

c14 drafted · lead 2–21 SEC

Scope: standard IEEE 1547-2018 proposed

Conditions: UV1 allowable clearing time settings, Category II; also UV2 clearing time range in Category III

c26 verified · fact 0–655 SEC

Scope: products CPS SCA100K-T-US-480 / SCA50K-T-US-208

Conditions: VoltMaxTripT1/T2/T3 overvoltage trip times

verified by: review-workflowverified on: 2026-10-24

c32 verified · fact 0–100 PERCENT

Scope: products CPS SCA100K-T-US-480 / SCA50K-T-US-208

Conditions: GridVoltMin1 level 1 undervoltage trip value, percent of nominal

verified by: review-workflowverified on: 2026-10-24

default_value

c25 drafted · lead nominal 110 PERCENT

Scope: products CPS SCA100K-T-US-480 / SCA50K-T-US-208

Conditions: GridVoltMax1 (level 1 overvoltage) in IEEE 1547, Rule 21 and ISO-NE profiles

review note: possible conflict with c30 (same source; check the conditions); possible conflict with c33 (same source; check the conditions)

c30 drafted · lead nominal 120 PERCENT

Scope: products CPS SCA100K-T-US-480 / SCA50K-T-US-208

Conditions: GridVoltMax2 and GridVoltMax3 in IEEE 1547, Rule 21 and ISO-NE profiles

review note: possible conflict with c25 (same source; check the conditions); possible conflict with c33 (same source; check the conditions)

c33 drafted · lead nominal 88 PERCENT

Scope: products CPS SCA100K-T-US-480 / SCA50K-T-US-208

Conditions: GridVoltMin1 in IEEE 1547, Rule 21 and ISO-NE profiles

review note: possible conflict with c25 (same source; check the conditions); possible conflict with c30 (same source; check the conditions)