Function

Limit maximum active power

ID
func:limit-active-power
IRI
https://solarlattice.org/kb/func/limit-active-power
Status
active
Also known as
active power limitation, power limiting, curtailment setpoint, WMaxLimPct, DWMX, Set active power limit, Active Power Limit, Maximum Active Power Limit, Active power limit ratio
Category
Control
Function kind
control

This function puts a cap on the active power a DER sends out. When it is enabled, the unit's output stays at or below a set maximum. Vendors configure it differently. Sungrow string inverters use an enable switch plus a limit ratio as a percentage of rated power. Huawei SUN2000 inverters take a maximum active power value in kW. SMA inverters use the parameter Set active power limit. On Tesla battery systems, the limit applies in the discharge direction. It is a per-unit fraction of nameplate real power, and both the limit and its enable flag can be read and written over Modbus. The SMA Cluster Controller receives active power limitation setpoints from the grid operator or a direct marketer as digital or analog signals or over Modbus, passes them to the inverters, and reports them back. When the setpoints conflict, it applies the one that limits power most. With self-consumption, the Cluster Controller uses closed-loop control based on the measured feed-in at the grid connection point. The inverters must be set to Act. power lim. via PV system ctrl, which requires installer login with an SMA Grid Guard code.

Claims

requires

c1 drafted · lead IEEE 1547-2018 4.6.2 Capability to limit active power proposed

Maximum Active Power setting range is referred to clause 4.6.2.

c2 drafted · lead SunSpec model 123 Immediate Controls

Scope: products KACO blueplanet 87.0-165 TL3

External power limitation on the KACO blueplanet is set through WMaxLimPct and WMaxLim_Ena in SunSpec model 123.

c3 drafted · lead Grid Guard code holder

Scope: products SMA Cluster Controller

Setting inverters to accept Cluster Controller active power limitation setpoints requires installer login and an SMA Grid Guard code.

review note: support check: partial - Procedure requires Installer login and Grid Guard code to enable inverters to accept Cluster Controller limits; the passage doesn't say the role 'holder' explicitly but it's essentially implied.

c4 drafted · lead Modbus

Scope: products Tesla Megapack platform (generation not stated) proposed

Tesla exposes the enable flag and the per-unit limit as read/write Modbus registers 22501 and 22502.

setting_range

c5 drafted · lead 0–100 PERCENT

Scope: products Sungrow SG250HX-US

Conditions: Active power limit ratio, expressed as a percentage of rated power

c6 drafted · lead ≥ 0.1 KiloW

Scope: products Huawei SUN2000-45KTL-US-HV-D0

Conditions: Maximum active power parameter; upper bound is Pmax_limit (device upper limit of maximum active power)

c7 drafted · lead ≥ 0.1 KiloW

Scope: products Huawei SUN2000-100KTL-USH0

Conditions: Maximum active power parameter; upper bound is Pmax_limit