An exhausted or tripped surge protection device has used up its protection, usually after a significant surge event, and no longer protects the inverter. The inverter raises an SPD warning, for example Warn0040 for the DC SPD or Warn0100 for the AC SPD on CPS inverters. SMA inverters show a fault overvoltage protector message. Check the SPD module by eye. A red indicator, sometimes with an audible alarm, means the SPD has been used up. The same warning can appear if the arrester is just not seated properly. A green indicator points to this. Replace any SPD module that shows red or has tripped. If the indicator is green, remove the module and seat it again in its socket. If the warning still does not clear, contact the manufacturer's service team. Some SPDs have dry alarm contacts that can report a failed unit remotely to a monitoring system.

<!-- review notes

<!-- review workflow 2026-10-20: dropped as unsupported

Claims

affects

c1 drafted · lead Surge protection device

c2 verified · fact Inverter

The inverter's built-in surge protection modules are replaced when needed. The CPS inverter raises warnings Warn0040 (DC SPD) and Warn0100 (AC SPD).

verified by: review-workflowverified on: 2026-10-20

caused_by

c3 verified · fact Voltage surge event

Eaton gives a significant surge event as the probable cause when the SPD shows its red indicator.

verified by: review-workflowverified on: 2026-10-20

presents_as

c5 verified · fact SPD status indicator red

On CPS inverters a red indicator means the SPD module must be replaced. A green indicator points to a seating problem.

verified by: review-workflowverified on: 2026-10-20

c6 verified · fact SPD audible alarm

verified by: review-workflowverified on: 2026-10-20

detected_by

c7 verified · fact Visual inspection

Look at the SPD status indicator.

verified by: review-workflowverified on: 2026-10-20

c8 verified · fact SPD alarm contact monitoring

Dry contacts switch to alarm if a thermal protector or fuse inside the SPD opens or a phase loses power. Normally-closed wiring is recommended because it also detects a cut wire.

verified by: review-workflowverified on: 2026-10-20

mitigated_by

c9 drafted · lead SPD replacement

c10 drafted · lead SPD module reseating

Applies when the indicator is green or the arrester may not be inserted correctly.

c11 verified · fact Contact manufacturer service

Use this if replacing or reseating the module does not clear the warning.

verified by: review-workflowverified on: 2026-10-20