FailureMode
Ground fault detector failure
- ID
fm:ground-fault-detector-failure
- IRI
https://solarlattice.org/kb/fm/ground-fault-detector-failure
- Status
- active
- Also known as
- Leakage current sensor fault, sensor fault of leakage current, GFCI sensor abnormal, GFCI sensor abnormality, Ground Fault Current Sensor Abnormal
The inverter has a residual current circuit, required by UL 1741, that detects leakage from ground faults in the PV array, raises an alarm and stops the inverter. This failure mode means the leakage current (GFCI) sensor in that circuit has failed. It does not mean there is a ground fault in the array. Depending on the model, the inverter shows protection code Protect0100 or Protect0310. You can see the code on the inverter display. It is also flagged in the Modbus fault register. First, turn both the AC and DC switches off, wait one minute for the energy to discharge, and turn them back on. If the fault does not clear, contact the manufacturer's service team to replace the filter board or the whole inverter.
<!-- review notes
- sentence 1: support check: partial - UL1741 residual current detection, alarm and ceasing operation are stated, but only in some passages and with a leakage threshold condition in others.
- sentence 2: support check: partial - Passages say sensor abnormal/fault, but nowhere state that it does not indicate an array ground fault.
- sentence 3: support check: partial - Both codes appear for the sensor fault, but the passages do not tie them to model differences.
- sentence 4: support check: partial - The Modbus register bit and LCD display are shown, but the LCD display appears only for Protect0100, and the register is a fault register with Fault1 storage.
- sentence 4: review: partial - All three rows place the fault at Modbus register 0x8402 Bit15 (two say Fault1), but only the 275kW map gives an LCD display value (Protect0100), so the passages do not show Protect0310 on the display.
-->
Claims
affects
c1 verified · fact
Ground fault detection circuit
The fault is in the leakage current (GFCI) sensor of the inverter's ground fault detection circuit.
verified by: review-workflowverified on: 2026-10-23
c2 drafted · lead
Filter board
CPS manuals name the filter board as a replacement part for this fault, so the sensor may sit on it.
review note: review: partial - The passages name the filter board as a replacement option, but they never say the fault affects the filter board or that the sensor is on it; the note only offers this as a guess.
presents_as
c3 verified · fact
Internal device fault
The inverter reports it as protection code Protect0100 (leakage current sensor fault) or Protect0310 (GFCI sensor abnormal), depending on the model.
verified by: review-workflowverified on: 2026-10-23review note: support check: partial - Codes Protect0100/Protect0310 are stated, but 'depending on the model' and the classification as an internal device fault are not explicit.
mitigated_by
c4 verified · fact
Inverter restart
Turn both AC and DC switches off, wait one minute for the energy to discharge, then turn them back on.
verified by: review-workflowverified on: 2026-10-23
c5 verified · fact
Filter board replacement
Do this if a restart does not clear the fault.
verified by: review-workflowverified on: 2026-10-23
c6 verified · fact
Inverter replacement
Do this if a restart does not clear the fault.
verified by: review-workflowverified on: 2026-10-23
c7 verified · fact
Contact manufacturer service
Contact after-sales or CPS service if the fault stays after a restart.
verified by: review-workflowverified on: 2026-10-23