FailureMode
Grid earthing system incompatibility
- ID
fm:earthing-system-incompatibility
- IRI
https://solarlattice.org/kb/fm/earthing-system-incompatibility
- Status
- active
- Also known as
- TN-C connection, IT grid, IT network not supported, Delta IT utility grid, improper PE connection, TT grid, touch voltage on enclosure, grid configuration, TN-C system, IT not supported, delta IT networks, earthing system compatibility, corner grounded Delta
This failure happens when an inverter is connected to a grid earthing system or grid configuration that the model does not support, such as an IT grid on a model without IT support, or a delta grid other than the one specified. Support depends on the model. Some hybrid models do not support IT networks and are not recommended for TN-C, while some commercial and utility models support all major earthing systems. On a TN-C system with a large load imbalance, a touch voltage can appear on the inverter enclosure. Connecting to an unsupported delta grid can damage the inverter. Before installing, verify the site earthing system and confirm it is compatible with the inverter model, using the manufacturer compatibility table and the installation manual. If TN-C cannot be avoided, keep the unbalanced output function disabled. Where possible, convert the installation to TN-C-S before connecting the inverter. Balance loads across the phases, and do not use a neutral terminal for loads when there is no neutral conductor. For non-standard topologies, contact the manufacturer and the utility. Never change earthing arrangements without approval from the electrical authority or a qualified engineer.
<!-- review notes
- sentence 7: support check: partial - The passages support contacting the manufacturer for non-standard topologies and never changing earthing without approval. Contacting the utility is only for exact connection specifications, not specifically for non-standard topologies.
- sentence 7: review: partial - The passages support contacting the manufacturer for non-standard topologies and never changing earthing without authority or engineer approval, but they mention the utility only for exact connection specifications in delta IT networks, not for non-standard topologies in general.
-->
Claims
affects
c1 drafted · lead
Inverter
Each inverter model supports only certain grid earthing systems or grid configurations; for example some hybrid models do not support IT grids, and TN-C is not recommended for them.
presents_as
c2 drafted · lead
Touch voltage on enclosure proposed
On TN-C systems, a large load imbalance can put a touch voltage on the inverter enclosure under some operating conditions.
caused_by
c3 drafted · lead
Installation error
Connecting the inverter to a grid topology or earthing system the model does not support. On one product line, delta grids other than the supported one may damage the inverter and void the warranty.
review note: support check: partial - The delta-grid damage and warranty caution is stated, but nothing explicitly names installation error as the cause. Only best practices that imply it are given.
c4 drafted · lead
Recurring line-to-ground faults proposed
On a 480 V delta service, co-located loads that cause recurring line-to-ground faults effectively turn it into a corner-grounded delta grid, which exposes the inverters to excessive line-to-ground voltage.
review note: support check: partial - u25 describes recurring line-to-ground faults on 480 V delta giving an effective corner-grounded delta and excessive line-to-ground voltage. It does not say this is an earthing incompatibility, and it prescribes isolating the PV system from the fault source.
mitigated_by
c5 drafted · lead
Earthing system verification proposed
Check the site earthing system and confirm it is compatible with the inverter model before installing.
c6 drafted · lead
TN-C-S conversion proposed
Where possible, convert a TN-C installation to TN-C-S before connecting the inverter.
c7 drafted · lead
Inverter settings review
If a TN-C connection cannot be avoided, the unbalanced output function must stay disabled.
c8 drafted · lead
Balanced phase loading proposed
On three-phase systems, balance loads across all phases. If there is no neutral conductor, do not connect loads to a neutral terminal.
c9 drafted · lead
Contact manufacturer service
Contact the manufacturer when the site topology or transformer configuration is outside the supported standard configurations.
c10 drafted · lead
Utility company consultation
Get the exact connection specifications from the electric utility; local regulations and distribution system operator requirements take priority.
c11 drafted · lead
Proper installation
A qualified electrician should do the work, following local regulations and the model-specific installation manual. Earthing arrangements should never be changed without approval.
Data