Concept
Point of interconnection
- ID
concept:point-of-interconnection
- IRI
https://solarlattice.org/kb/concept/point-of-interconnection
- Status
- active
- Also known as
- POI, PCC, point of common coupling, point of connection, Netzverknüpfungspunkt
- Category
- Grid
- Concept kind
- electrical
The point of interconnection (POI), often called the point of common coupling (PCC), is where a customer's local electric power system connects to the utility's area electric power system. It is the point on the utility grid that other customers are connected to, or could be connected to. In most cases the PCC matches the service point as defined in the NEC and the NESC. It is different from the point of DER connection, which is where the DER unit itself connects inside the local system. Grid connection rules say whether a requirement applies at the point of interconnection or at the inverter terminals, and the grid operator or local regulations choose which reference point to use. Inverters often have settings tied to this point, such as a Voltage PCC Set value required under Rule 21, or the nominal apparent power at the PCC. Large plants also use the POI for metering and for grid strength checks: a revenue busway meter may be required at the POI, and inverter limits are given in terms of short-circuit ratio at the POI. Under the NEC, each interactive system's point of interconnection with other sources must be labeled at the disconnecting means. Examples include AC combining panels, AC disconnects and backfed breakers.
<!-- review notes
- sentence 6: support check: partial - Busway meter at POI is required for Utility Hybrid systems, and SCR at POI appears in inverter tables, but 'revenue' meter and 'large plants' are not stated.
-->
Claims
related_to
c1 drafted · lead
Point of common coupling proposed
SMA glossaries define PCC as the point of interconnection on the utility grid that other customers are or could be connected to.
c2 verified · fact
Area electric power system
The PCC is where a Local EPS connects to the Area EPS.
verified by: review-workflowverified on: 2026-10-24
c3 verified · fact
Local electric power system proposed
verified by: review-workflowverified on: 2026-10-24
c4 drafted · lead
Reference point of applicability proposed
Grid connection requirements may apply at the point of interconnection or at the inverter terminals; the grid operator or local regulations decide which.
c5 drafted · lead
Short-circuit ratio
Inverter configuration limits for weak grids are given in terms of the SCR at the POI.
review note: support check: partial - Passages show SCR values at the POI for inverter configurations, but do not clearly state weak-grid limits; the tables are fragmentary.; review: partial - The table rows tie SCR values at the POI to inverter configurations, but no quoted passage says these are configuration limits or that they apply to weak grids.
c6 verified · fact
Energy meter
For Tesla Utility Hybrid systems, one busway meter at the point of interconnection is required.
verified by: review-workflowverified on: 2026-10-24
c7 drafted · lead
Islanding
An island is energized by Local EPSs through their associated PCCs.