Concept
Grid impedance
- ID
concept:grid-impedance
- IRI
https://solarlattice.org/kb/concept/grid-impedance
- Status
- active
- Also known as
- network impedance, source impedance, virtual grid impedance, ZPCC, Grid LV impedance
- Category
- Grid
- Concept kind
- electrical
Grid impedance is the electrical impedance of the utility network as seen from the connection point of a PV or storage system, usually derived from the short-circuit power available at the point of common coupling. When a PV system injects power, the impedance of the feeder causes the voltage at the connection point to rise in proportion to the power injected. A low grid impedance means a stiff grid that can absorb a lot of PV power before voltage limits are reached, while a high value points to a resistive feeder or one already loaded with much PV. Impedance between inverters and the grid, including conductors and transformers, can push terminal voltage up enough to cause over-voltage trips and also affects the stability of inverter controls. Some inverters report an event and disconnect from the grid when the grid voltage or grid impedance at their connection point is too high. Weak, high-impedance grids can produce low-frequency resonance between paralleled string inverters and the network, so designers check grid impedance at the PCC and keep short-circuit power well above plant size. For most commercial systems the grid capacity at the PCC dwarfs the PV system, so grid impedance is negligible and the utility supplies the value when it is needed. Related concepts include voltage rise, short-circuit ratio, transformer impedance and symmetrical components.
<!-- review notes
- sentence 1: support check: partial - The passages tie ZPCC to short-circuit power at the PCC, but they don't define grid impedance as the utility network impedance seen from the connection point or say it is 'usually' derived that way.
- sentence 8: support check: partial - Voltage rise, short-circuit power and transformer impedance, and sequence components are all discussed, but the passages don't state them as 'related concepts' of grid impedance; short-circuit ratio appears only as an Ssc/Splant requirement.
- sentence 1: review: partial - The passages tie ZPCC to the short-circuit power available at the PCC, but they never define grid impedance as the utility network's impedance seen from the connection point, nor say it is 'usually' derived that way.
-->
Claims
explains
c1 drafted · lead
Voltage rise
Impedance between the PV system and the grid raises the voltage seen at the inverter terminals; injected power raises voltage at the connection point roughly in proportion.
c2 drafted · lead
Inverter-grid resonance at low short-circuit ratio
High-impedance (weak) grids can cause low-frequency resonance instabilities between the grid and paralleled inverters; inverter control stability depends on impedance to the PCC.
related_to
c3 drafted · lead
Short-circuit ratio
Schneider recommends calculating grid impedance at the PCC and keeping short-circuit power at least 8 times plant installed power.
c4 drafted · lead
High grid impedance
SMA inverters disconnect from the grid when grid voltage or impedance at the connection point is too high.
c5 drafted · lead
Point of interconnection
Grid impedance is evaluated at the point of common coupling from the available short-circuit power.
c6 drafted · lead
Voltage drop
AC conductors should limit voltage drop between inverters and PCC to a maximum of 1% of nominal voltage.
c7 drafted · lead
Medium voltage transformer
Transformer short-circuit impedance adds to total system impedance seen by the inverter.
c8 verified · fact
Symmetrical components
Source impedance is expressed as positive-, negative- and zero-sequence components in fault analysis.
verified by: review-workflowverified on: 2026-10-24review note: support check: partial - u28 lists positive-, negative- and zero-sequence source impedances in fault analysis, but it doesn't call this 'grid impedance' explicitly, though it is the utility source impedance.
Referenced by
Data