Solar Lattice

Architecture

Functionally grounded PV array

ID
arch:functionally-grounded-pv-array
IRI
https://solarlattice.org/kb/arch/functionally-grounded-pv-array
Status
active
Also known as
functional grounding, functionally grounded, Functional Grounded PV System, Grounded, Functionally, DC Grounded
Category
Earthing

A functionally grounded PV array has an electrical reference to ground, but it is not solidly grounded. The ground connection is usually made through a fuse, a circuit breaker, a resistance device, a non-isolated grounded AC circuit, or electronics inside the inverter that are part of a listed ground-fault protection system. Conductors that normally sit at ground potential can carry voltage to ground during a fault, so test them before you touch them. The NEC lists a 2-wire PV array with one functionally grounded conductor as an allowed system grounding configuration, next to bipolar, ungrounded and solidly grounded arrays. Most modern string inverters are functionally grounded and non-isolated. Most legacy systems installed before 2011 had one DC pole solidly bonded to ground in the inverter. Solectria XGI 1500-1MW and XGI 1500-DCG inverters ground the DC input or DC negative, for example through the GFDI breaker. This prevents potential induced degradation in modules that are susceptible to it. On the XGI 1500-1MW, you can switch the DC input to floating in the user interface. Floating is the normal setting for DC-coupled storage, where the battery must float. When you retrofit a site whose modules need positive or negative grounding, ask the module manufacturer before you install a functionally grounded inverter. The change may expose the modules to potential induced degradation.

<!-- review notes

Referenced by

Data