Solar Lattice

Symptom

Transfer switch not detected

ID
symptom:transfer-switch-not-detected
IRI
https://solarlattice.org/kb/symptom/transfer-switch-not-detected
Status
active
Also known as
no ATS has been detected

A Generac PWRcell inverter reports wiring error 0X7720 when it is set up for AC generator integration but cannot find an automatic transfer switch (ATS). The NumTranSwtchs setpoint tells the inverter how many external transfer switches are installed and turns on transfer switch control. It must be 2 for AC generator integration and 1 for AC coupled PV. Check first that the Cat 5 cables for the ATS and the CTs are undamaged and plugged into the correct inverter ports. Then confirm that the ATS limit switch is wired to the Auxiliary Contact port on the PWRcell ATS Controller. The reverse condition, code 0X7721, means an ATS was detected but the inverter is not configured for one. Fix it by setting NumTranSwtchs to match the number of installed ATSes. AC generator integration does not support a single-ATS setup or transfer switches from other manufacturers. Confirm the hardware matches the supported layout.

Claims

observed_as

c1 drafted · lead Inverter fault code display

Generac PWRcell inverter shows wiring error code 0X7720 when it is set up for AC generator integration but cannot detect an ATS.