Grid reconnection conditions not met

ID
symptom:reconnection-limits-not-met
IRI
https://solarlattice.org/kb/symptom/reconnection-limits-not-met
Status
active
Also known as
Grid frequency or voltage outside the permissible range for reconnection, FrqCtl.ReconMax, VolCtl.ReconMax, Event 15 or 1501

After a grid fault the inverter stays off the grid because the measured grid frequency or voltage is outside the allowed range for reconnection. Some country standards use tighter limits for reconnection than for normal operation, for example an upper reconnection frequency of 50.05 Hz under VDE AR-N 4105, and the most common cause is a frequency that is too high. The inverter itself is not faulty and switches back on by itself once frequency and voltage have stayed inside the range for the grid monitoring time. First, read out the live grid frequency and voltage, the country standard and the reconnection limits over the communication interface, then compare them with your own grid measurement. A voltage reading taken after the trip may look normal, because grid voltage at the inverter drops as soon as feed-in stops. Look for large local loads such as machines that make the grid fluctuate. If the grid itself is out of range, the grid operator decides on fixes or on allowing changed inverter settings. In rare cases the cause is an incorrect or edited country data set (grid code misconfiguration). Reloading the original data set for the installation country fixes this.

<!-- review notes

Claims

observed_as

c1 verified · fact Grid frequency outside limits

After a disturbance some country standards apply stricter reconnection limits than the trip limits. The frequency is usually above the upper reconnection limit.

verified by: review-workflowverified on: 2026-10-24review note: support check: partial - Passages support frequency outside reconnection limits (ReconMax/ReconMin, usually too high), but the signal details like W staying at zero until frequency returns are not stated.

c2 verified · fact Grid voltage outside limits

Grid voltage falls right after feed-in stops, so a reading taken after the trip may rarely show a value above the set limits.

verified by: review-workflowverified on: 2026-10-24

c3 verified · fact Grid OK flag false

Islanding controller output that is true only when grid voltage and frequency are within the reconnect thresholds.

verified by: review-workflowverified on: 2026-10-24

c4 verified · fact Inverter fault code display

SMA reports this condition as event 15 or 1501.

verified by: review-workflowverified on: 2026-10-24