Symptom

PV input overload

ID
symptom:pv-input-overload
IRI
https://solarlattice.org/kb/symptom/pv-input-overload
Status
active
Also known as
PV overload condition

PV input overload is an inverter alarm. It means the PV array connected to the inverter inputs is delivering more than the inverter is designed to accept. On the Schneider Conext CL125 it shows up as event or alarm code 076, also read over Modbus as hex 0x004C, with the description PV overload condition. The manufacturer's fix is to review the PV system design and change how the PV strings are connected to the inverter inputs. Check the array sizing and how strings are spread across the PV inputs first, because the alarm points to a design or connection issue rather than a failed part. Do not confuse this alarm with the CL125 PV power event warning, code 078. That one points to loose PV input terminals that need re-torquing.