Meter wiring reversed

ID
symptom:meter-wiring-reversed
IRI
https://solarlattice.org/kb/symptom/meter-wiring-reversed
Status
active
Also known as
reversed CT polarity

The meter or its current transformers have been wired the wrong way round, for example with the meter's input and output connections swapped. First check whether the meter is connected correctly and whether its input and output wiring is reversed. If an existing system is enabled, also check the rated power setting of the existing inverter. A related wiring error is a voltage reference that does not match its CT phase. Current and voltage then read normal, but power comes out lower than expected. In that case, check the power factor in the monitoring portal. Two phases reading 0.5 and -0.5 means those two phases are swapped. Trace the wiring between the meter and the feeder against the wiring diagram. Do not rely on meter validity alarms to catch this: some controllers do not detect reversed CT polarity, so check meter wiring at commissioning.