Solar Lattice

Symptom

Flat capped output

ID
symptom:flat-capped-output
IRI
https://solarlattice.org/kb/symptom/flat-capped-output
Status
active

Flat capped output means the plant or inverter power trace runs as a flat line during good sun and does not follow rising irradiance. When the flat top sits at the inverter AC rating on sunny days, it points to inverter clipping, where the array can supply more DC power than the inverter can deliver as AC. Clipping is often a planned design choice that buys extra morning and evening yield, so it is not always a fault. When the flat level sits below the inverter rating, or below the power the irradiance should support, it points to grid curtailment from operator dispatch, an interconnection limit, a plant controller command, a reaction to negative prices or a site export cap. During curtailment, inverter and tracker availability can look normal, so it is easy to log as underperformance by mistake. Check plant setpoints, inverter active power limits, dispatch records, meter output, battery charging behavior and curtailment flags before looking for equipment faults. Do not confuse this with an inverter voltage floor: clipping caps power, while voltage flooring is an MPPT limit caused by the DC voltage window.

<!-- review notes

Claims

observed_as

c1 verified · fact Flat output below available power

Grid curtailment signature: output held at a flat or controlled level below what irradiance supports, while inverter and tracker availability may look normal.

verified by: review-workflowverified on: 2026-10-20