Solar Lattice

Symptom

Feed-in above export limit

ID
symptom:export-limit-exceeded
IRI
https://solarlattice.org/kb/symptom/export-limit-exceeded
Status
active
Also known as
Supplied power has exceeded the permitted value, zero feed-in control deviation, Inverter does not respond to active power limitation, Exporting at night, Export limit exceeded, phase feeding into the grid despite zero export, control deviations of 1-2 kW

This symptom means more active power is fed into the grid at the point of connection than the export limit allows, even though export limitation is switched on. It shows in the system logbook as a message that supplied power has exceeded the permitted value several times, or that an inverter does not respond to active power limitation. On export control monitoring screens, a red status bar means exported power is above the limit, while yellow means it is inside the guard band below the limit. A short exceedance after a sudden load change is normal because the control cannot fully prevent it, but it is limited in time; repeated or lasting exceedance points to an export control fault. Check the feed-in or energy meter first: confirm it works and is wired correctly, since a failed or wrongly installed meter breaks the control loop. If the meter is fine and the message keeps coming back, check the inverter active power operating mode so it follows the external or system control setpoint. If an inverter does not respond to limitation, the controller curtails the other inverters harder to stay within the limit; if the exceedance message also appears on the same day, there is a real fault. Check the guard band or negative limit settings too: they give the control a safety margin against load steps and meter inaccuracy.

<!-- review notes

Claims

observed_as

c1 verified · fact Exported power above limit proposed

Export control monitoring shows a red status bar when power exported at the point of connection is over the export limit; a brief red bar after a positive load step is normal, and a red bar is a trigger for a fallback plan.

verified by: review-workflowverified on: 2026-10-24review note: support check: partial - Red bar over export limit, normal brief red after load step, and fallback trigger are stated, but the 'derating off / inverter not curtailed' condition is not stated as such.

c2 verified · fact Export limit exceeded event proposed

SMA Sunny Home Manager event 10520 logged when power fed in exceeded the permitted value several times although active power limitation is enabled.

verified by: review-workflowverified on: 2026-10-24

c3 verified · fact Inverter ignores power limit event proposed

SMA event 10525: at least one inverter does not respond to active power limitation; the controller curtails the remaining inverters harder to keep within the limit.

verified by: review-workflowverified on: 2026-10-24