DC injection monitoring error

ID
symptom:dc-injection-monitoring-error
IRI
https://solarlattice.org/kb/symptom/dc-injection-monitoring-error
Status
active
Also known as
DC feed-in monitoring, sampling offset of DCI

This symptom is the inverter's internal check of DC injection on its AC output reporting an error. It does not mean that high DC injection has been measured. Inverters treat DC injection of the AC output as a protection function and a variable they monitor all the time. On Fronius Primo and Symo inverters it shows up as status code 462, an error in the DC feed-in monitoring routine. Keep this separate from the DCinj-FAULT alarm on other inverters. That alarm reports that high DC injection current was actually detected. For Protect0180, first check whether the inverter will start up. If it does, recalibrate it. If the alarm keeps returning and the inverter cannot start, replace the inverter.