Solar Lattice

Symptom

Anti-islanding protection disabled

ID
symptom:anti-islanding-disabled
IRI
https://solarlattice.org/kb/symptom/anti-islanding-disabled
Status
active
Also known as
SPUI, Special Purpose Utility-Interactive, Active Anti islanding Disabled, Passive Anti islanding Disabled

On a Fronius Symo, this condition appears on the display as state code 581. The code means the Special Purpose Utility-Interactive setup has been activated. In this mode the islanding function is switched off, power is reduced depending on frequency, and the frequency and voltage limits are changed. The inverter then no longer meets IEEE1547. Fronius says code 581 is not an error, and the operator confirms it with the Enter key. Even so, check that the deactivated islanding protection was intended for this site. Keep this separate from code 456, which means the anti-islanding function has stopped running properly. That is a malfunction, not a deliberate setting. On some other products, anti-islanding methods can be turned on or off through configuration settings. These include active reactive pulse, frequency shift, frequency drift and passive checks. Some manufacturers allow only qualified personnel to disable anti-islanding, while Solis inverters ship with it enabled and it cannot be disabled. Anti-islanding protection comes built in on Fronius Symo inverters, so if it is found disabled, look first at the setup configuration.

<!-- review notes

Claims

observed_as

c1 drafted · lead Inverter fault code display

Fronius Symo shows state code 581 when the Special Purpose Utility-Interactive (SPUI) setup is active. Islanding protection is then deactivated and the unit no longer complies with IEEE1547. The manual says this is not an error: confirm the code with the Enter key.

the islanding function is deactivated, frequency-dependent power reduction is activated, and the frequency and voltage limits are being changed

Referenced by

Data