Solar Lattice

OperatingState

Power limited

ID
state:power-limited
IRI
https://solarlattice.org/kb/state/power-limited
Status
active
Also known as
active power limitation, curtailed, export limited, setpoint limited, limited operation, Limited Export, Power reduction, Power limiting, Nameplate Limits, Active power limited AC voltage
Category
Inverters

Power limited means the inverter is running normally but is held below the power it could otherwise deliver, because of a setpoint, an export limit or its own nameplate rating. On SMA Inverter Manager systems, the limit can be a fixed active power setpoint (P_ref). It can also be sent dynamically through the I/O Box, Modbus or a direct marketer interface, and a dynamic value overrides the fixed one. With Limited Export and a Modbus energy meter, the limit applies at the grid connection point. Inverter output rises or falls with on-site consumption, so local loads are still supplied. Indications differ by vendor. Solectria inverters keep the green LED on and show messages such as L1 Power reduction or PV1 PW limit to Pn. FIMER inverters show LIMxxx% with a code giving the cause. SMA systems log an event that reports how many minutes active power was limited that day. A limit set by the nameplate rating needs no action. If the limit comes from low grid voltage and does not go away, check the grid voltage and contact the grid operator. If an anti-islanding limit stays active while the inverter is still connected to the grid, contact customer assistance. Hours with heavy curtailment can make the performance ratio look low even when the equipment is healthy. Take this into account before you look for a fault.

<!-- review notes

Claims

output_limit

c1 verified · fact nominal 50 PERCENT

Scope: products FIMER PVS-60-TL-US string inverter

Conditions: Worked example in the manual: a display reading of LIM 50% means output is held to 50% of nominal output power. In this case the limit comes from low grid voltage (CODE:04).

verified by: review-workflowverified on: 2026-10-24

c2 verified · fact nominal 50 PERCENT

Scope: products UNO-DM-3.3/3.8/4.6/5.0-TL-PLUS-US string inverter

Conditions: Worked example in the manual: a display reading of LIM 50% means output is held to 50% of nominal output power. In this case the limit comes from the anti-islanding function (CODE:03).

verified by: review-workflowverified on: 2026-10-24

c3 verified · fact 0–100 PERCENT

Conditions: SMA reports active power limitation as active when the default limitation value is above 0% and below 100%.

verified by: review-workflowverified on: 2026-10-24

Referenced by

Data