Product
Solectria PVI 50-60TL
- ID
prod:yaskawa-solectria-pvi-50-60tl
- IRI
https://solarlattice.org/kb/prod/yaskawa-solectria-pvi-50-60tl
- Status
- active
- Also known as
- PVI 50 60 TL, PVI 50TL-480, PVI 60TL-480
- Category
- Inverters
- Make
- yaskawa-solectria
- Product level
- family
The Solectria PVI 50-60TL is a family of three-phase string inverters made up of the PVI 50TL-480 and PVI 60TL-480 models. The breaker selection table lists the PVI 50TL-480 at 50 or 55 kVA and the PVI 60TL-480 at 60 or 66 kVA. The suggested maximum AC breaker is 125 A. For AC overcurrent protection, the PVI 50TL-480 needs at least an 80 A breaker at 50 kVA or a 90 A breaker at 55 kVA. The PVI 60TL-480 needs at least a 100 A breaker at either of its ratings. The inverters support standard Modbus communication over RS-485, and third-party data acquisition systems must connect through a shielded twisted-pair RS-485 link. Monitoring through SolrenView requires the optional Ethernet Network Card. The same card can send data to the YConnect Pro portal, which handles remote diagnostics and automatic firmware upgrades.
<!-- review notes
- sentence 1: support check: partial - Models 50TL-480 and 60TL-480 are listed, but 'three-phase string inverter' family is not stated in the passages.
- sentence 1: review: partial - The passages list the PVI 50TL-480 and PVI 60TL-480 models, but none of them say these are three-phase string inverters.
-->
Claims
instance_of
c1 drafted · lead
Inverter
review note: support check: partial - Passage says the PVI 50TL-480 and 60TL-480 are inverters, but never names a combined 'PVI 50-60TL' product or explicitly says inverter class beyond calling them inverters; core is fine.
uses_protocol
c2 drafted · lead
Modbus
Modbus carried over RS-485.
c3 drafted · lead
RS-485
Third-party monitoring connects over a shielded twisted-pair RS-485 link.
c4 drafted · lead
Ethernet
Only with the optional Ethernet Network Card, which SolrenView monitoring and YConnect Pro remote diagnostics need.
review note: support check: partial - Ethernet Network Card is optional and needed for SolrenView, and YConnect Pro data goes via it, but the passages don't explicitly say YConnect Pro needs it or name Ethernet as a protocol.; review: partial - The passages say the optional Ethernet Network Card is needed for SolrenView and lets data go to YConnect Pro, but they do not say YConnect Pro requires the card.
implements
c5 verified · fact
Remote firmware update
Uses the optional Ethernet Network Card and the YConnect Pro portal.
verified by: review-workflowverified on: 2026-10-24
rated_power
c6 drafted · lead
nominal 50 KiloV-A
Conditions: PVI 50TL-480 at the 50 kVA rating; the AC breaker selection table gives a minimum AC OCPD of 80 A
review note: possible conflict with c7 (same source; check the conditions); possible conflict with c8 (same source; check the conditions); possible conflict with c9 (same source; check the conditions)
c7 drafted · lead
nominal 55 KiloV-A
Conditions: PVI 50TL-480 at the 55 kVA rating; the AC breaker selection table gives a minimum AC OCPD of 90 A
review note: possible conflict with c6 (same source; check the conditions); possible conflict with c8 (same source; check the conditions); possible conflict with c9 (same source; check the conditions)
c8 drafted · lead
nominal 60 KiloV-A
Conditions: PVI 60TL-480 at the 60 kVA rating; the AC breaker selection table gives a minimum AC OCPD of 100 A
review note: possible conflict with c6 (same source; check the conditions); possible conflict with c7 (same source; check the conditions); possible conflict with c9 (same source; check the conditions)
c9 drafted · lead
nominal 66 KiloV-A
Conditions: PVI 60TL-480 at the 66 kVA rating; the AC breaker selection table gives a minimum AC OCPD of 100 A
review note: possible conflict with c6 (same source; check the conditions); possible conflict with c7 (same source; check the conditions); possible conflict with c8 (same source; check the conditions)
Referenced by