Product
Acrel DTSD1352 meter
- ID
prod:acrel-dtsd1352
- IRI
https://solarlattice.org/kb/prod/acrel-dtsd1352
- Status
- active
- Also known as
- DTSD1352, Acrel DTSD 1352, Solis 3phase Meter DTSD1352, 3Phase meter DTSD1352
- Category
- Metering
- Make
- acrel
- Product level
- family
The Acrel DTSD1352 is a three-phase energy meter that Solis lists as a supported meter for its three-phase grid-tied inverters. It comes in two versions: an inline 80 A version for sites under 40 kW, and a version that uses external CTs with a 5 A secondary. Connected to a compatible Solis inverter, the meter supports the inverter's internal export power limit and consumption monitoring. Examples are the S5-GR3P, S5-GC and S6-GC3P series. Larger S6-GC models use 300 A CTs. The meter ships with three Acrel AKH-.66 K24 150A:5A CTs, so the CT ratio should be 30, which is primary current divided by secondary current. Change the ratio if you use other 5 A CTs. If the meter readings do not match the actual loads, check the CT ratio. You set it through the In and CT menus and must save it on the Save screen, or the change is lost. The sources give different setup codes: one gives an initial password of 0001, another says to enter 0008. For a three-phase three-wire LV network, set the wiring system to 3P3L in the PL screen of the SYS menu, then save.
<!-- review notes
- sentence 5: support check: partial - Passages say to check the CT ratio if readings look wrong and describe In/CT menus and saving, but do not explicitly say the change is lost if not saved.
-->
Claims
manufactured_by
c1 drafted · lead
Acrel proposed
review note: support check: partial - Passages name it an Acrel DTSD1352 meter, but none state that Acrel is its manufacturer explicitly beyond the naming.
implements
c2 drafted · lead
Export limitation
Gives Solis three-phase grid-tied inverters the meter input they need for their internal export power limit function.
c3 drafted · lead
Consumption metering proposed
compatible_with
c4 drafted · lead
Acrel AKH-0.66 K24 CT proposed
Conditions: Three 150A:5A CTs are supplied with the meter (external CT, 5 A secondary variant).
c5 drafted · lead
Solis S5-GR3P(3-20)K proposed
Conditions: Inline 80 A version for sites under 40 kW, or with external 5 A CTs.
c6 drafted · lead
Solis S5-GC(25-40)K proposed
Conditions: Inline 80 A version for sites under 40 kW, or with external 5 A CTs.
c7 drafted · lead
Solis S6-GC3P(25-36)K03-NV-ND proposed
Conditions: Inline 80 A version for sites under 40 kW, or with external 5 A CTs.
c8 drafted · lead
Solis-3P(3-20)K-4G proposed
Conditions: Inline or external 5 A CT versions.
c9 drafted · lead
Solis S6-GC(80-125)K proposed
Conditions: Only the external 5 A CT version, using 300 A CTs.
c10 drafted · lead
Solis S6-EH1P(3-8)K-PLUS proposed
Conditions: External 5 A CT version, only when the hybrid inverters run in parallel.
review note: support check: partial - S6-EH1P(3-8)K-PLUS is listed under the external CT DTSD1352 entry 'when parallel', but the 'only' and 5A-version phrasing is inferred; the entry lists the DTSD1352 with 5A CT secondary, which broadly fits.