Solar Lattice

Product

Acrel DTSD1352 meter

ID
prod:acrel-dtsd1352
IRI
https://solarlattice.org/kb/prod/acrel-dtsd1352
Status
active
Also known as
DTSD1352, Acrel DTSD 1352, Solis 3phase Meter DTSD1352, 3Phase meter DTSD1352
Category
Metering
Make
acrel
Product level
family

The Acrel DTSD1352 is a three-phase energy meter that Solis lists as a supported meter for its three-phase grid-tied inverters. It comes in two versions: an inline 80 A version for sites under 40 kW, and a version that uses external CTs with a 5 A secondary. Connected to a compatible Solis inverter, the meter supports the inverter's internal export power limit and consumption monitoring. Examples are the S5-GR3P, S5-GC and S6-GC3P series. Larger S6-GC models use 300 A CTs. The meter ships with three Acrel AKH-.66 K24 150A:5A CTs, so the CT ratio should be 30, which is primary current divided by secondary current. Change the ratio if you use other 5 A CTs. If the meter readings do not match the actual loads, check the CT ratio. You set it through the In and CT menus and must save it on the Save screen, or the change is lost. The sources give different setup codes: one gives an initial password of 0001, another says to enter 0008. For a three-phase three-wire LV network, set the wiring system to 3P3L in the PL screen of the SYS menu, then save.

<!-- review notes

Claims

manufactured_by

c1 drafted · lead Acrel proposed

review note: support check: partial - Passages name it an Acrel DTSD1352 meter, but none state that Acrel is its manufacturer explicitly beyond the naming.

implements

c2 drafted · lead Export limitation

Gives Solis three-phase grid-tied inverters the meter input they need for their internal export power limit function.

c3 drafted · lead Consumption metering proposed

compatible_with

c4 drafted · lead Acrel AKH-0.66 K24 CT proposed

Conditions: Three 150A:5A CTs are supplied with the meter (external CT, 5 A secondary variant).

c5 drafted · lead Solis S5-GR3P(3-20)K proposed

Conditions: Inline 80 A version for sites under 40 kW, or with external 5 A CTs.

c6 drafted · lead Solis S5-GC(25-40)K proposed

Conditions: Inline 80 A version for sites under 40 kW, or with external 5 A CTs.

c7 drafted · lead Solis S6-GC3P(25-36)K03-NV-ND proposed

Conditions: Inline 80 A version for sites under 40 kW, or with external 5 A CTs.

c8 drafted · lead Solis-3P(3-20)K-4G proposed

Conditions: Inline or external 5 A CT versions.

c9 drafted · lead Solis S6-GC(80-125)K proposed

Conditions: Only the external 5 A CT version, using 300 A CTs.

c10 drafted · lead Solis S6-EH1P(3-8)K-PLUS proposed

Conditions: External 5 A CT version, only when the hybrid inverters run in parallel.

review note: support check: partial - S6-EH1P(3-8)K-PLUS is listed under the external CT DTSD1352 entry 'when parallel', but the 'only' and 5A-version phrasing is inferred; the entry lists the DTSD1352 with 5A CT secondary, which broadly fits.