Phase voltage spread alert
This alert fires when the measured phase voltages of a three-phase meter or inverter no longer match each other closely. One monitoring platform ships it as a default meter voltage alert that checks the phase voltages stay within 5% of each other. The inputs are the individual phase RMS voltages, or the line voltages between phase pairs such as A-B and B-C. Power meters can also report the spread as a percent negative-sequence or zero-sequence voltage imbalance, refreshed every 10 or 12 cycles. When phase voltages differ, one meter manual says to first check whether a low supply voltage is present. The same manual says to also check that the connected load type is not variable, because a variable load can cause unequal phase voltages. Some inverters have a configurable grid voltage imbalance threshold, so a large spread can also cause an inverter protection event.