ID
meas:negative-sequence-voltage-imbalance
IRI
https://solarlattice.org/kb/meas/negative-sequence-voltage-imbalance
Status
active
Also known as
V_IMB, V_IMB_n

Negative-sequence voltage imbalance is a three-phase power quality value that a revenue meter reports as a percentage. The meter works it out from the ratio of the negative-sequence voltage component to the positive-sequence component. The instantaneous value is refreshed every 10/12 cycles, and the meter can also record an aggregated version whose update rate depends on the aggregation period. If the positive-sequence voltage is very low, the meter reports the imbalance as zero, so a zero reading during an outage does not mean the phases are balanced. The meter also reports the negative-sequence voltage magnitude in volts, updated every half-cycle, which helps you read the percentage in context. Negative sequence means a set of equal three-phase quantities rotating in the opposite order to the normal sequence, so a rising percentage shows the phase voltages are moving away from a balanced set.

<!-- review notes

Signals

Monitoring channels where this signature appears, named by SunSpec model point.

PointUnitPattern
model_103.PhVphAVphase voltage deviates from the other phases instead of tracking them