ID
meas:negative-sequence-current-imbalance
IRI
https://solarlattice.org/kb/meas/negative-sequence-current-imbalance
Status
active
Also known as
I_IMB, I_IMB_n, Aggregated negative-sequence current imbalance

Negative-sequence current imbalance is a revenue meter quantity, labeled I_IMB and reported as a percentage, that shows how unbalanced the three phase currents are. The meter calculates it by comparing the negative-sequence current component with the positive-sequence component. A negative-sequence set is three equal-magnitude quantities 120 degrees apart that rotate in the opposite order to normal, so maxima occur as ACB instead of ABC. The meter updates the value every 10/12 cycles, and an aggregated version, I_IMB_n, updates once per configured aggregation period. If the positive-sequence current is below 10 mA, the meter reports this imbalance as zero, so a zero reading at very low load does not show the phases are balanced. Read it together with negative-sequence voltage imbalance and zero-sequence current imbalance, which the meter reports in the same table. A current transformer connected to the wrong tap is one wiring error that can be found by measuring negative-sequence current and comparing expected with measured current magnitudes.

<!-- review notes

Signals

Monitoring channels where this signature appears, named by SunSpec model point.

PointUnitPattern
model_103.AAphase currents unequal at steady output