Meter vs display mismatch

ID
meas:meter-display-mismatch
IRI
https://solarlattice.org/kb/meas/meter-display-mismatch
Status
active

This signature compares two readings. One is the PV input voltage you measure with a meter at the DC terminals in the wiring box. The other is the voltage the inverter shows in its measurement data menu. Manuals tell you to make this check when the inverter raises a PV overvoltage protection code, such as PVVoltOver or PV2VoltOver. A mismatch means the display reading falls outside a 2% band around the meter reading. In that case the manuals treat the inverter's own measurement as untrustworthy and say to replace the inverter. If the display agrees with the meter within that band, the overvoltage is real. The fix is then to change the number of modules in the string or source circuit. The open-circuit PV voltage limit you check against depends on the model. Several manuals give 1000V, and one 1500V-class central inverter manual gives 1500V.