Also known as
SoC, SOC
Category
Storage
Concept kind
technology

State of charge is the amount of charge that can still be drawn from a battery, given as a percent of its nominal capacity, where 100% means full and 0% means empty. For example, if 25 Ah is taken from a 100 Ah battery, its state of charge is 75%. Inverters such as the Sunny Island work out state of charge by counting ampere-hours in and out of the battery, then correct it using full-charge detection and battery voltage. After a boost, full or equalization charge, the calculated value is reset, and an estimated error value shows how accurate the current reading is. Lithium-ion batteries that have their own battery management system send their state of charge to the inverter, and the BMS uses it to adjust charge limits. If the battery is not brought to full charge from time to time, cells can drift apart and the displayed value can stop matching the real state of charge, so periodic calibration matters. Example conservation ranges are 60% to 65% for lead-acid and 25% to 30% for lithium-ion, and backup reserve and depth of discharge settings are also expressed against state of charge. A charge controller regulates battery state of charge in most PV systems with battery storage.

<!-- review notes

Claims

related_to

c1 drafted · lead SoC estimation methods

SOC is found by ampere-hour counting with full-charge detection, plus recalibration from battery voltage.

c2 drafted · lead PV charge controller

Most PV systems with battery storage need a charge controller to regulate battery state of charge.

c3 verified · fact Float charge

Float charge ends when SOC drops below 70% of available charging capacity; reaching 100% by float charge takes several days.

verified by: review-workflowverified on: 2026-10-24

c4 drafted · lead Battery charging stages

SOC is reset to 90%, 95% or 100% after boost, full or equalization charge respectively, under default settings.

c5 drafted · lead Lead-acid battery

With lead-acid batteries the Sunny Island needs several cycles to calculate SOC correctly and shows 50% after commissioning.

c6 drafted · lead Lithium-ion battery

A lithium-ion BMS reports SOC to the inverter and adjusts charge limits using SOC.

c7 drafted · lead Backup reserve

review note: support check: partial - Backup reserve percentages and a state-of-charge maintenance range appear, but no explicit relation between SOC and backup reserve is stated.

c8 drafted · lead Depth of discharge

review note: support check: partial - Depth of discharge is shown with percentage figures, but SOC itself and its relation are not explicitly stated.