Solar Lattice

Concept

Power quality

ID
concept:power-quality
IRI
https://solarlattice.org/kb/concept/power-quality
Status
active
Also known as
voltage sags, swells, flicker, rapid voltage change, PQ
Category
Grid
Concept kind
electrical

Power quality describes how well the electricity supply suits the equipment that uses it. A power quality problem is any deviation in voltage, current or frequency that makes customer equipment misoperate or fail. Common power quality events include voltage sags (also called dips), swells, interruptions, flicker, harmonic distortion and phase unbalance. A voltage sag is a sudden drop in voltage while the load stays connected. Faults on the power system usually cause sags, but starting large motors can also cause them. A rapid voltage change is a quick shift in rms voltage between two steady states that stays inside the sag and swell thresholds. Switching, inrush currents and energizing a transformer can all cause one. Power quality problems can come from the utility, from your own site's equipment, or from a neighbouring facility. Equipment that is sensitive to disturbances can also be the source of them. Revenue and protection meters, such as Class A meters built to IEC 61000-4-30, log sags, swells, flicker and harmonics for this kind of analysis. Power quality analysis is also part of PV commissioning.

<!-- review notes

Claims

related_to

c1 drafted · lead Point of common coupling proposed

Rapid voltage change and flicker limits are judged at the PCC, and the utility may record flicker at or near the PCC.

c2 drafted · lead Harmonic distortion

Harmonics and THD are tracked as power quality parameters.

c3 drafted · lead Phase unbalance

Voltage and current unbalance are logged as power quality events or parameters.

c4 drafted · lead Load inrush current

Start-ups, inrush currents and the switching of capacitor banks or transformers are listed as causes of rapid voltage changes.

c5 drafted · lead IEEE 519 proposed

One utility points to IEEE 519 as guidance when it reviews flicker data.

c6 drafted · lead Power quality analyzer

Where flicker is a concern, the utility may install a recording power quality meter.

c7 drafted · lead SEL-735 Power Quality and Revenue Meter proposed

This meter complies with IEC 61000-4-30 Class A and measures flicker, sags, swells and interruptions.

c8 drafted · lead Accuenergy Acuvim II power meter

It logs power quality events such as sags and swells, each with a timestamp.

Referenced by

Data