Array boundary

ID
concept:array-boundary
IRI
https://solarlattice.org/kb/concept/array-boundary
Status
active
Also known as
inside the array boundary, outside the array boundary
Category
Safety
Concept kind
electrical

The array boundary is a term from the NEC rapid shutdown rules: the zone extending 305 mm (1 ft) from the PV array in all directions. Where a controlled conductor sits relative to this boundary decides which rapid shutdown limit applies to it: 690.12(B)(1) outside, 690.12(B)(2) inside. Outside the boundary, or more than 1 m (3 ft) past the point of entry into a building, controlled conductors must drop to 30 volts or less within 30 seconds of rapid shutdown initiation. Voltage is measured between any two conductors and between any conductor and ground. Inside the boundary, the system can use a listed or field-labeled rapid shutdown PV array. Otherwise, controlled conductors must drop to 80 volts or less within 30 seconds. In one manufacturer's commercial guide, the inverter DC input circuits stay inside the array boundary. The AC output circuits run outside it and meet the outside-boundary limit once the AC breaker or AC disconnect is opened. Ways to comply include module-level power electronics or a UL 3741 listed array, and sub-arrays can be kept within the same array boundary. The purpose of rapid shutdown is to reduce shock hazard for emergency responders working on buildings with PV.

<!-- review notes

Claims

related_to

c1 verified · fact PV rapid shutdown

The array boundary decides which rapid shutdown voltage limits apply to controlled conductors.

verified by: review-workflowverified on: 2026-10-24

c2 drafted · lead NEC 2017 690.12(B)(2) Rapid shutdown: controlled conductors inside the array boundary proposed

Inside the boundary, the options are a listed rapid shutdown PV array, or controlled conductors limited to 80 V within 30 s, or the exemption for arrays with no exposed wiring or conductive parts.

c3 drafted · lead PV array

The boundary is measured from the array in all directions.

c4 drafted · lead UL 3741 proposed

A Solis guide describes an upper array that meets the inside-boundary requirement through a UL 3741 listing without MLPEs.

c5 drafted · lead Module-level power electronics

In the guide's example, MLPEs control the circuits on a lower sub-array to meet 690.12(B)(1) and (B)(2).

c6 drafted · lead Electric shock

Rapid shutdown, which is organized around the array boundary, reduces shock hazard for emergency responders.