Concept
Arc flash incident energy
- ID
concept:arc-flash-incident-energy
- IRI
https://solarlattice.org/kb/concept/arc-flash-incident-energy
- Status
- active
- Also known as
- incident energy, arc flash boundary, cal/cm2, PPE category, IE
- Category
- Safety
- Concept kind
- electrical
Incident energy is the heat energy a worker could receive at a given working distance from an arc flash, and it decides what level of PPE the worker must wear and how far the arc flash boundary sits. The clearing time of the upstream protective device is a key factor; clearing in the instantaneous range can keep incident energy below 8 cal/cm2 for many industrial conditions. Under NFPA 70E the arc flash boundary is the distance where incident energy falls to 1.2 cal/cm2, so higher incident energy pushes the boundary farther out. For DC equipment such as PV inverters and combiners, calculation methods have little test backing; EPRI field tests found that measured incident energy rose linearly with PV array size. In battery storage, a DC arc flash study found worst-case incident energy of 22.746 cal/cm2 at 18 inches on an unfused stack, which corresponds to PPE category 4. The equipment label shows the available incident energy or the PPE category, and the analysis must be reviewed at least every 5 years or whenever the system changes.
<!-- review notes
- sentence 1: support check: partial - IE dictating PPE level and boundary is stated, and working distance is mentioned, but the definition as heat energy a worker receives is not explicit, and boundary is defined by 1.2 cal/cm2 rather than directly decided.
- sentence 6: support check: partial - Label contents and the 5-year review and update on system changes are stated, but the review applies to incident energy analysis and label data, and the label option includes other items; 'at least every 5 years' is fine though the label may show other options.
-->
Claims
related_to
c1 drafted · lead
AC arc flash
Incident energy calculations for AC arc flash are well established and backed by industry tests.
c2 drafted · lead
DC arc flash
For DC systems such as PV and battery storage, incident energy calculation methods are not backed by standardized methods or broad testing.
c3 drafted · lead
IEEE 1584 proposed
IEEE 1584 provides the main industry equations for AC incident energy and arc flash boundary calculations.
c4 verified · fact
Arc-rated clothing
Arc-rated clothing is selected according to the incident energy at the task working distance.
verified by: review-workflowverified on: 2026-10-24
c5 drafted · lead
Personal protective equipment proposed
c6 drafted · lead
Arc flash hazard assessment proposed
c7 verified · fact
Arc flash labeling proposed
Labels carry available incident energy with working distance, or the PPE category, plus the arc flash boundary.
verified by: review-workflowverified on: 2026-10-24
c8 drafted · lead
Overcurrent protection
The protective device clearing time at the arcing current largely determines incident energy.
c9 verified · fact
Powin Stack750 / Centipede proposed
A DC arc flash study calculated worst-case incident energy for this battery system.
verified by: review-workflowverified on: 2026-10-24