Solar Lattice

Component

Voltage sensor

ID
comp:voltage-sensor
IRI
https://solarlattice.org/kb/comp/voltage-sensor
Status
active
Also known as
measurement circuit

A voltage sensor measures voltage so that a monitoring system or an inverter can check it against expected or allowed values. In one research monitoring system, each PV module had its own voltage sensor, built as a voltage divider, alongside a current sensor. Readings from these sensors, plus irradiance and temperature, were compared with a neural network prediction, and a module was flagged for maintenance when predicted and actual power differed by more than 10%. In Canadian Solar three-phase inverters, an under grid voltage alarm (UN-G-V) may come from a bad voltage measurement circuit rather than a truly low grid voltage. This is the voltage measurement sensor fault. To check, switch the DC off, measure AC at the inverter test points and compare it with the voltage shown on the LCD. A low reading on the display with a normal measured value points to the measurement circuit. If the alarm stays after the grid standard has been checked with the DC switch on, the manual says to replace the inverter. These inverters carry protective circuits and controls so that they meet the relevant codes and standards.

<!-- review notes

Referenced by

Data