When the RCD between the utility and the inverter trips, the inverter is disconnected from the grid and stops feeding in. Other loads on the same RCD also lose power. In monitoring data this shows up as the inverter's AC output going to zero, with no inverter fault behind it. The RCD sees the inverter's normal leakage current as residual current. So the rated residual current set in the inverter must not be higher than the RCD's rating, and it can be set lower if the RCD trips often. An RCD with a lower rating than the inverter manufacturer specifies can cause false trips, depending on system design. Check the RCD's type and rating against the inverter's datasheet first. A known firmware defect on some SMA Smart Energy inverters caused RCD trips. It affected systems with an RCD rated 100 mA or higher and a connected backup port, and a firmware update fixes it. Also check that fuses and breakers installed in series work together selectively, so that devices further upstream do not trip by mistake. If the trips keep happening, photograph the device that is tripping and send the pictures to the inverter manufacturer's support team.

<!-- review notes

Claims

observed_as

c1 verified · fact Zero inverter AC output

When the upstream RCD trips, the inverter is cut off from the grid and stops feeding in. Any other loads on the same RCD also lose power.

verified by: review-workflowverified on: 2026-10-24review note: support check: partial - Passage says the inverter is disconnected and stops feeding in, but doesn't mention AC power/voltage signal behavior or that phase voltage is lost; the signal details are inferred.

Data