Solar Lattice

Symptom

Battery not detected by inverter

ID
symptom:battery-not-detected
IRI
https://solarlattice.org/kb/symptom/battery-not-detected
Status
active
Also known as
battery is not detected in installation wizard, cannot detect batteries or backup box, battery not recognized, Battery not recognized by inverter, no detection of the battery, no communication with battery

This symptom shows up during commissioning or in the installation wizard: the hybrid or storage inverter cannot find the connected battery, and sometimes it cannot find the backup box either. The most common cause is a communication bus fault: the battery-to-inverter cabling is wrong, the communication cable is not suitable, the CAN termination is faulty, or the Enable and GND lines are miswired. Other possible causes are an inverter that is not grounded correctly, inverter firmware that is out of date, an incomplete battery firmware update, or a defect in the CAN interface of the inverter or of the battery management system. If the wiring checks out, the internal COM plug may have come loose. Signs of this are a missing supply voltage between pins 2 and 4 of the COM connector, or an open (very high) resistance between pins 1 and 3. On REbus-based systems, start with the basics: the inverter must be enabled, the DC disconnect must be on, connections must be secure, the inverter and battery must use the same PLM channel, and the REbus voltage must be high enough. A CAN interface functional test does not need the battery connected. It can rule out an inverter defect, but it is not a full check of the CAN bus. If the battery side is still suspected, contact the battery manufacturer.

<!-- review notes

Claims

observed_as

c1 verified · fact Open bus termination resistance proposed

Measured between pin 1 and pin 3 of the COM connector with the inverter disconnected on AC and DC sides; about 120-140 ohm is expected, while a reading toward infinity points to the internal COM plug having come loose.

verified by: review-workflowverified on: 2026-10-24

c2 verified · fact Missing communication supply voltage proposed

With the inverter switched on and the COM connector unplugged, about 11-12 V is expected between pin 2 and pin 4; if it is absent, suspect a loose internal COM plug.

verified by: review-workflowverified on: 2026-10-24

c3 verified · fact Low REbus voltage proposed

Generac PWRcell: the REbus terminals should show at least 360 V between RE+ and RE-. The REbus voltage can also be checked on the inverter control panel home screen.

verified by: review-workflowverified on: 2026-10-24review note: support check: partial - The passages give the 360 V minimum between RE+ and RE- and say REbus voltage can be verified on the inverter control panel home screen. They don't name Generac PWRcell, though the REbus and PLM terms point to it.