SunSpec model 132 is the Volt-Watt information model. It is a defined group of registers that sets up a voltage-dependent active power curve, P(U). The Solectria XGI 1500 implements model 132 in its Modbus map. The ModEna bitfield turns Volt-Watt control on, and it is off by default. The NPt register is read-only and reports how many curve points the array holds. Its default is 10. Each curve point has a read-write voltage register (V1 to V10) expressed in percent of Vref, with an unscaled setting range of 0-1200. Each point also has a watts register (W1, W2 and so on) with an unscaled range of 0-1000. On the XGI 1500, only the listed models are supported, and registers marked Reserved within a model should not be used. SMA SunSpec profile 2.0 no longer supports model 132. In that profile, model 706 DER Volt-Watt replaces it.