Solar Lattice

Protocol

Common Smart Inverter Profile

ID
proto:csip
IRI
https://solarlattice.org/kb/proto/csip
Status
active
Also known as
CSIP, SunSpec Common Smart Inverter Profile
Category
Communication
Protocol kind
application

CSIP, the SunSpec Common Smart Inverter Profile, appears in equipment datasheets as a grid interoperability certification. The Generac PWRcell 2 inverter lists CSIP among its grid certifications, alongside UL 1741 SB, IEEE 1547 and Rule 21. In an Enphase system, the IQ Gateway software runs an IEEE 2030.5 client that exchanges messages with a utility CSIP server. The CSIP server can send a Power Export Limit (PEL) command, and the gateway applies the default PEL to the grid profile. An Enphase gateway release fixed problems where the 2030.5 client stopped responding when the CSIP server did not answer its first message. The same release added timeout and retry handling. The same release also fixed a problem where CSIP PEL commands did not reduce IQ8 output in sites that mix IQ7 and IQ8 microinverters.

<!-- review notes

Referenced by

Data