This is Cooper Power Systems' family of three-phase pad-mounted, compartmental-type distribution transformers, built in the United States. Standard ratings run from 45 kVA up to 12000 kVA at 50 or 60 Hz, and custom ratings can be ordered. High-voltage ratings range from 2400 V to 46 kV. Units are filled with either electrical grade mineral oil or Envirotemp FR3, a less-flammable, biodegradable fluid suited to fire-sensitive sites. Applicable units are designed to meet or exceed the DOE 2010 efficiency values under 10 CFR Part 431, and the transformer products are ISO 9001 compliant. A VFI version pairs the transformer with a resettable vacuum fault interrupter that gang-trips all three phases on a fault or overload, so three-phase loads are never left single-phased. An optional sealed visible break window lets the operator check whether the loadbreak switch contacts are open or closed before starting maintenance.
<!-- review notes
manufactured_byc1 drafted · lead Cooper Power Systems proposed
sec=h43 h=2b82d9eecf4csec=h45 h=34c38ff4492csec=h2 h=09e9ac97bfe2rated_powerc2 drafted · lead 45–12000 KiloV-A
Conditions: Standard three-phase kVA ratings listed for 50 or 60 Hz; custom ratings also available
tbl=2 h=75803a3f98e3review note: review: partial - Table 2 lists standard three-phase 50 or 60 Hz ratings from 45 to 12000 kVA, but the passage says nothing about custom ratings (the footnote marker 1 is not quoted).
frequencyc3 drafted · lead nominal 50 HZ
Conditions: 50 Hz three-phase ratings
tbl=2 h=75803a3f98e3review note: possible conflict with c4 (same source; check the conditions)
c4 drafted · lead nominal 60 HZ
Conditions: 60 Hz three-phase ratings
tbl=2 h=75803a3f98e3review note: possible conflict with c3 (same source; check the conditions)
nominal_voltageConditions: Lower end of the available high-voltage (primary) range
sec=h2 h=09e9ac97bfe2Conditions: Upper end of the available high-voltage (primary) range
sec=h2 h=09e9ac97bfe2verified by: review-workflowverified on: 2026-10-24
certified_toc7 drafted · lead DOE 10 CFR Part 431 (2010) proposed
Applicable transformers are designed to meet or exceed DOE 2010 final rule efficiency values
sec=h38 h=50f5446d1009review note: support check: partial - Passages say units are designed to meet or exceed DOE 2010 efficiency under 10 CFR 431, but not that they are certified.
c8 drafted · lead ISO 9001 proposed
The manufacturer's transformer products are stated to be ISO 9001 compliant
sec=h2 h=09e9ac97bfe2review note: support check: partial - Passage says products are ISO 9001 compliant, not certified; the note itself reflects compliance only.
compatible_withc9 drafted · lead Cargill Envirotemp FR3 fluid
Offered with either electrical grade mineral oil or Envirotemp FR3 fluid
sec=h2 h=09e9ac97bfe2compatible_with c3