Solar Lattice

Product

3M 5815 Series modular splicing system

ID
prod:3m-5815-splicing
IRI
https://solarlattice.org/kb/prod/3m-5815-splicing
Status
active
Also known as
3M 5815, 5815 Series, Modular Splicing System
Category
Connectors and cable
Make
3m
Product level
family

The 3M 5815 Series is a modular, fully shielded 600 A separable connector system. It is used to splice, tap and dead-end medium-voltage shielded power cable, and to connect cable to deadfront apparatus. The kits are rated for 5, 8, 15 and 25 kV class industrial shielded cables, and connections are rated up to 25 kV. The system meets ANSI/IEEE 386 for 600 A dead-break interfaces and connects to transformers, switches and switchgear that have 600 A bushings. Kits can be combined for 3-way, 4-way and parallel feed tap configurations, and modules can be added or removed later. The basic 5815-S kit is a two-way splice that can be disconnected to isolate circuits for maintenance. Every cable needs its own 5815-B Series adapter kit, which fits the tee module to the cable size. A T-Wrench tool is available for kits that include connecting plugs. A capacitive test point on the insulating plug lets you test the circuit without disturbing the bolted connection. The finished installation is suitable for submerged or direct burial locations. It suits tape shield, wire shield, UniShield and jacketed concentric neutral solid dielectric cables rated for 90 °C operation and 130 °C emergency overload. Freezing does not harm the components.

<!-- review notes

Claims

manufactured_by

c1 drafted · lead 3M Electrical Markets proposed

review note: support check: partial - Passages describe the 3M 5815 Series but none name 3M Electrical Markets as the maker (only the 3M brand mark).

instance_of

c2 drafted · lead MV separable connector proposed

Fully shielded 600 A separable insulated connector system for shielded power cable.

certified_to

c3 drafted · lead ANSI/IEEE 386 proposed

Meets ANSI/IEEE 386 requirements for 600 A dead-break interfaces.

review note: support check: partial - Passages say it meets ANSI/IEEE 386 requirements, but not that it is certified.

requires

c4 drafted · lead 3M 5815-B adapter kit proposed

One adapter kit is needed per cable connected; adapter kits fit the tee modules to specific cable sizes.

review note: support check: partial - An adapter kit is required per cable, and 5815-B Series adapter kits fit cable sizes, but a specific '5815-B adapter kit' product is a series, not singly named.

nominal_voltage

c5 drafted · lead 5–25 KiloV

Conditions: Cable voltage class rating of the kits (5, 8, 15 and 25 kV shielded power cables)

c6 drafted · lead ≤ 25 KiloV

Conditions: Voltage rating of completed connections

rated_output_current

c7 drafted · lead nominal 600 A

Conditions: Continuous current rating of the separable connector system

operating_temperature

c8 drafted · lead nominal 90 DEG_C

Conditions: Rated operating temperature of the shielded power cable the system is used on

review note: possible conflict with c9 (same source; check the conditions)

c9 drafted · lead nominal 130 DEG_C

Conditions: Emergency overload rating of the shielded power cable the system is used on

review note: possible conflict with c8 (same source; check the conditions)