Parameter file reload

ID
mit:reload-parameter-file
IRI
https://solarlattice.org/kb/mit/reload-parameter-file
Status
active

Reloading the parameter file is the corrective action for SMA STP inverter event 7102. That event means the parameter file was not found or is defective, so loading it failed. The inverter keeps feeding in while this event is active, so the problem does not stop production. To fix it, copy the parameter file into the correct folder again. Event 10118 confirms the fix worked: it reports that the parameter upload is complete and the configuration file loaded. Event 7105 is a related case where parameters could not be set from the memory card. For that one, check that the parameters are set correctly and that you have an SMA Grid Guard code. The operating manual has a separate procedure for adopting a configuration from a file.