The capacity test checks how much power the system can generate. It can be run with the ASTM regression method or with the PKs method. To get measured capacity, output power is fitted by multiple linear regression against plane-of-array irradiance, ambient air temperature and wind speed. The data come from a short collection period, typically 3 to 30 days. The reporting conditions are then put into the regression equation, which gives a capacity in watts. Expected capacity is found the same way, but using simulated power from a performance model of the system. That model is driven by meteorological data covering at least 5 contiguous days. The comparison only means something if both capacities use the same reporting conditions and the simulation period matches the data collection period. The comparison between expected and measured capacity can be used as a criterion for accepting the plant.
c1 verified · fact
ASTM E2939 proposed
ASTM E2939 sets out how to find the expected capacity and the reporting conditions. That expected capacity is meant to be compared with the capacity measured under Test Method E2848. The edition cited is E2939-13, approved September 2013.