Some plant controllers expose feedback points that report back the real and reactive power setpoints the device is applying. You can compare these with the setpoints the dispatcher sent. The real power feedback points are reported per unit of rated power (Wpu), and the reactive power feedback points per unit of rated reactive power (Varpu). Check that the commanded values use the same per-unit scaling before you call it a mismatch. A mismatch can be expected behaviour. A controller treats a setpoint as invalid if no configuration exists for it or if it falls outside the configured value range. It then applies fallback setpoints instead of the commanded value. If no setpoint arrives within a configurable time, the controller keeps the last valid value for a limited time and then switches to the configured fallback values. It returns to the current setpoint once a valid one is received again. On some central inverters, invalid content in the power setpoint information shows up as the ComInvalid display message. The fix is to check the power specification settings. Event logs that record when the setpoint specification was activated or deactivated help show which setpoint source was active when the mismatch occurred.